Parameters/address space
4.2 Parameters
Analog input module F-AI 4xI 0(4)..20mA 2-/4-wire HF (6ES7136-6AA00-0CA1)
Manual, 08/2018, A5E41448857-AB
21
Parameters
Value range
Default
Parameter reas-
signment in RUN
Scope
Behavior after channel faults
•
Passivate entire mod-
ule
•
Passivate channel
Passivate channel
No
Module
Reintegration after channel
fault
•
Adjustable
•
All channels automati-
cally
•
All channels manually
(S7-300/400) Adjusta-
ble
(S7-1200/1500) All
channels manually
No
Module
F-I/O DB manual number
assignment
•
Disable
•
Enable
Disable
No
Module
F-I/O DB number
—
suggested by F-
system
No
Module
F-I/O DB name
—
suggested by F-
system
No
Module
AI parameters
Interference frequency sup-
pression
•
50 Hz
•
60 Hz
50 Hz
No
Module
Channel parameters:
Channel n
Sensor evaluation
•
1oo1 evaluation (max.
SIL3/Cat.3/PLd)
•
1oo2 evaluation (max.
SIL3/Cat.4/PLe)
1oo1 evaluation (max.
SIL3/Cat.3/PLd)
No
Channel
Standard value
•
MIN
•
MAX
MIN
No
Channel
Discrepancy time *
100 to 30000 ms
100 ms
No
Channel
Tolerance window %, abso-
lute
2.0 to 20.0%
5.0%
No
Channel
Tolerance window %, relative 2.0 to 20.0%
5.0%
No
Channel
Activated
•
Disable
•
Enable
Enable
No
Channel
Channel fault acknowledg-
ment
•
Manual
•
Automatic
The value range offered
depends on the F-CPU in
use and on the configura-
tion of the F-parameter
"Reintegration after chan-
nel fault".
(S7-300/400) Parame-
ter is not supported
(S7-1200/1500) Man-
ual
No
Channel
Measuring range
•
0 to 20 mA
•
4 to 20 mA
4 to 20 mA
No
Channel