Applications of the F-I/O module
5.1 Application 1: Safety mode SIL3/Cat.3/PLd with 2-wire transducer
Analog input module F-AI 4xI 0(4)..20mA 2-/4-wire HF (6ES7136-6AA00-0CA1)
Manual, 08/2018, A5E41448857-AB
43
Assignable parameters for application 1
Table 5- 1
Parameters for application 1 of F-AI 4xI 0(4)..20mA 2-/4-wire HF
Parameters
Range of values in safety mode
Behavior after channel faults
•
Passivate the entire F-module
•
Passivate channel
Interference frequency suppression
•
50 Hz
•
60 Hz
Sensor evaluation
1oo1 evaluation (max. SIL3/Cat.3/PLd)
Measuring range
•
0 ... 20 mA
•
4 ... 20 mA
Diagnostics: Wire break
(in the measuring range 4 to 20 mA)
•
Disable
•
Enable
Smoothing
1 / 2 / 4 / 8 / 16 / 32 / 64 conversion cycles