Siemens Energy & Automation, Inc.
46
Order Number
Order Number
Nominal
Size of the
Softstarter
Fuse
Current of Fuse
Fuse
MLFB
MLFB
A
3RW3454-0DC?4
3NE1021-0
100
00
3RW3455-0DC?4
3NE1225-0
200
1
3RW3457-0DC?4
3NE1230-0
315
1
3RW3458-0DC?4
3NE1331-0
350
2
3RW3465-0DC?4
3NE1331-0
350
2
3RW3466-0DC?4
3NE1331-0
350
2
3RW3467-0DC?4
3NE1331-0
450
2
3RW3472-0DC?4
3NE1435-0
560
3
3RW3483-0DC?4
3NE1438-1
800
3
3RW3484-0DC?4
3NE1438-1
800
3
3RW3486-0DC?4
2 x 3NE1438-1
2 x 800
3
Nominal Voltage 400 V
A
Ap
pp
pe
en
nd
diix
x A
A
Fuse protection coordination Type 2 for 3RW34 with SITOR fuses 3NE1...-0 (short circuit and conductor protection).
Order Number
Order Number
Nominal
Size of the
Softstarter
Fuse
Current of Fuse
Fuse
MLFB
MLFB
A
3RW3454-0DC?4
3NE1820-0
80
000
3RW3455-0DC?4
3NE1225-0
200
1
3RW3457-0DC?4
3NE1230-0
315
1
3RW3458-0DC?4
3NE1230-0
315
1
3RW3465-0DC?4
3NE1230-0
315
1
3RW3466-0DC?4
3NE1230-0
315
1
3RW3467-0DC?4
3NE1332-0
400
2
3RW3472-0DC?4
3NE1334-0
500
2
3RW3483-0DC?4
3NE1436-0
630
3
3RW3484-0DC?4
2 x 3NE1334-0
2 x 500
2
3RW3486-0DC?4
2 x 3NE1436-0
2 x 630
3
Fuses listed are the best selection based on reduced aging which also reduces the SIKOSTART rating (e.g. 3 x Ie for 5 seconds).