Main Voltage Required (± 15%)
In Line Application: 200/460V AC or 400/600V AC
(specified by catalog no.)
Inside Delta Application: 200/400V AC or
400/600V AC (specified by catalog no.)
Control Voltage Required
24V DC, 120V AC, or 230V AC, +10%, -15%
(specified by catalog no.)
Control power requirements are listed below.
AC Frequency & Phase
50/60 Hz, working 45 to 65 Hz; 3 phase
Temperature Range
0
v
to 50
v
C (32
v
to 122
v
F), inside enclosure in which unit is
mounted.
Derate 33% for each 10
v
C over 50
v
C to a max-
imum of 70
v
C.
Permissible Altitude
1000m at rated output
2000m at 0.87*le
3000m at 0.77*le
Overcurrent Protection
The standard SIKOSTART controller is not equipped with
overload protection.
The user must provide overload
protection.
Ratings for Frequent Starts and
Occasional
- 20 times in any
60 minute
period:
Stops, Plugging or Jogging Applications
Controller rating to be 133% of motor rating.
Severe
- 5 times in any
60 second
period:
Controller rating to be 200% of motor rating.
Very Severe
- 10 times in any
60 second
period:
Controller rating to be 300% of motor rating.
Controller Current Ratings
During Start and Run:
Current
Cold Start Time @ 50
vv
C
115%
Continuous
200%
480 sec.
300%
120 sec.
450%
30 sec.
500%
20 sec.
600%
10 sec.
Adjustment Ranges -
16 settings each:
Start Time (Accel Ramp)
.5 to 60 seconds*
Stop Time (Decel Ramp)
.5 to 60 seconds
Initial Voltage
30% to 80% of nominal voltage (approximately 10% to 64% on
normal starting torque)
*Acceleration time of the motor will probably be less than the
Start Time setting and will vary depending on the load friction
and inertia characteristics of the system.
Input (RUN) Coil
Coil Voltage
120VAC
24VDC
230VAC
Isolation Voltage, VAC
1500
1500
1500
Input Current, ma
10@120VAC
10@24VDC
10@230VAC
On Voltage, volts min.
85 VAC
17 VDC
170 VAC
On Current, ma min.
6ma
6ma
6ma
Off Voltage, volts max.
40VAC
8VDC
80VAC
Off Current, ma max.
3ma
3ma
3ma
Input Impedance,
ohms (typical)
13k
13k