Siemens Energy & Automation, Inc.
32
User Outputs
Rating
N.O. outputs are rated 0.5 Amp maximum at
Three solid state outputs are
24V DC, and 1.0 Amp at 120V AC and 230V AC.
available for the user to apply
User Output
ISOL Logic to Power
1500 VAC
Rating
10 Amp Make
1 Amp Break
1 Amp Continuous @ 120VAC
On Voltage Drop
1.2 VAC (typ)
Off Leakage Current
2 ma (typ)
Input Coil
ISOL Voltage
1500 VAC
Input Current
10 ma @ 120VAC
On Voltage
85VAC min.
On Current
6 ma min.
Off Voltage
40 VAC max.
Off Current
3 ma max.
Input Impedance
13K Ohm (typ)
Solid State Outputs
M (RUN)
When controller is operating, the RUN contact is closed.
Um = 100%
When motor is running at 100% of line voltage (after starting is
complete), the Um contact is closed.
FAULT
The FAULT contact closes for: an EEPROM error; a line voltage
phase loss; or a shorted thyristor.
Refer to paragraph 6.1 re
SW1-4 settings.
Recommended Fuse Style *
Two levels of short circuit protection can be provided by the user:
1. Type 1 protection is available where the short circuit protective device protects
the wiring and the integrity enclosure. The controller will probably damage and
require replacement or repair befoe being re-energized. Cirucit breakers and
motor circuit protectors provide this type of protection.
2. Type 2 protection is available where the short circuit protective device protects
both the wiring and the controller. The controller should not require repair
before re-energizing after the short circuit has been cleared. Fuses of an KR-1
type or HRC-1 type sized in accordance with the NEC/CEC code or semicon-
ductor type fuses provide this kind of protection.
Type RK-1 Dual Element
Partial List of Manufacturers
Bussman
LPN-RK
(250V or less)
LPS-RK
(600V or less)
Gould
A2D( )R
(250V or less)
A2D( )R
(600V or less)
Littelfuse
LLN-RK
(250V or less)
LLS-RK
(600V or less)
* For a complete listing of Siemens SITOR™ fuses, see Appendix A.