Power supply
8.1 Direct voltage supply provided by customer
ATE500E
System Manual, 09/2017, A5E33917696-AD
107
EMC
Immunity according to EN 61000-6-2:2005, Table 3, Table 3 – Interference immunity – direct
current network inputs and outputs. The limit values for the conducted interference emission
according to EN 50121-3-2:2006 are observed without filter. Conducted interference
emission is not defined for direct current supply according to EN 61000-6-4:2007+A1:2011.
If, however, the limits of EN 61000-6-4:2006, Table 2 – Interference emission – low voltage
alternating current supply are to be applied, a corresponding filter, e.g. of the type EPCOS
(B84112-B-B110), is to be installed upstream.
8.1.2
Installation
A miniature circuit breaker (type SIEMENS: 5SY4108-7 or 5SY4108-7KK11) is mandatory at
a direct voltage supply by the customer (for example SITOP PSU300S 20A).
1
Install the miniature circuit breaker in the vicinity of the SIDOOR controller (similar ambient
air temperature).
X3.1
Connection of ungrounded SELV voltage
typically 24 V
Plus
X3.2
Functional grounding
X3.3
Connection of ungrounded SELV voltage
typically 24 V
Minus
8.1.3
Wiring instructions
Observe the Wiring instructions (Page 60).
Содержание SIDOOR ATE500E
Страница 1: ......
Страница 53: ...Controller 6 4 Operation and parameter assignment ATE500E System Manual 09 2017 A5E33917696 AD 53 ...
Страница 54: ...Controller 6 4 Operation and parameter assignment ATE500E 54 System Manual 09 2017 A5E33917696 AD ...
Страница 56: ...Controller 6 4 Operation and parameter assignment ATE500E 56 System Manual 09 2017 A5E33917696 AD ...
Страница 57: ...Controller 6 4 Operation and parameter assignment ATE500E System Manual 09 2017 A5E33917696 AD 57 ...
Страница 58: ...Controller 6 4 Operation and parameter assignment ATE500E 58 System Manual 09 2017 A5E33917696 AD ...
Страница 95: ...Motor 7 2 Installation ATE500E System Manual 09 2017 A5E33917696 AD 95 ...