Table B-3
Bit-Type Data - Coil
Address
Modbus Data Type
Parameters
Access
1
Coil
Activate self-test mode
R/W
2
Coil
Reset device
R/W
3
Coil
Reset fault
R/W
4
–
Reserved for future use
–
5
Coil
Digital output 1
R/W
6
Coil
Digital output 2
R/W
7
Coil
Clear data available status
R/W
8
Coil
Clear event database
R/W
9
Coil
Initiate auto calibration
R/W
10
Coil
Energy counter reset
R/W
11
Coil
Password reset coil
R/W
12
Coil
Active-group switching
R/W
For more information about bit-type data - discrete inputs, see
.
Table B-4
Bit-Type Data - Discrete Inputs
Address
Modbus Data Type
Parameters
Access
1
Discrete Input
Status data/data available
R
2
Discrete Input
Self-test mode activated
R
3
Discrete Input
Overcurrent (I>>), high-set without direction
indication
R
4
Discrete Input
Ground-fault detection (I
N
>)
R
5
Discrete Input
Overvoltage warning (V
max
Warning)
R
6
Discrete Input
Overvoltage alarm (V
max
Alarm)
R
7
Discrete Input
Undervoltage warning (V
min
Warning)
R
8
Discrete Input
Undervoltage alarm (V
min
Alarm)
R
9
Discrete Input
I>/I>> direction A
R
10
Discrete Input
I>/I>> direction B
R
11
Discrete Input
I
N
> direction A
R
12
Discrete Input
I
N
> direction B
R
13
Discrete Input
Forward (A) power-flow direction of I
1
R
14
Discrete Input
Reverse (B) power-flow direction of I
1
R
15
Discrete Input
Forward (A) power-flow direction of I
2
R
16
Discrete Input
Reverse (B) power-flow direction of I
2
R
17
Discrete Input
Forward (A) power-flow direction of I
3
R
18
Discrete Input
Reverse (B) power-flow direction of I
3
R
19
Discrete Input
Time synchronization required
R
20
Discrete Input
Overcurrent warning
R
21
Discrete Input
Overcurrent alarm
R
22
Discrete Input
Overcurrent stage I>, low-set without direction
indication
R
23
Discrete Input
Phase-fault indication (I>/I>>)
R
24
Discrete Input
Phase-fault indication (I>/I>>) for at least 3 s
R
25
Discrete Input
Device-health status
R
Modbus Registers
B.2 Implementation of the Modbus Protocol
96
SICAM, Feeder Condition Monitor, Manual
E50417-H8940-C580-A4, Edition 03.2019
Содержание SICAM
Страница 8: ...8 SICAM Feeder Condition Monitor Manual E50417 H8940 C580 A4 Edition 03 2019 ...
Страница 11: ...Delivery 1 1 Delivery 12 1 SICAM Feeder Condition Monitor Manual 11 E50417 H8940 C580 A4 Edition 03 2019 ...
Страница 92: ...92 SICAM Feeder Condition Monitor Manual E50417 H8940 C580 A4 Edition 03 2019 ...
Страница 170: ...170 SICAM Feeder Condition Monitor Manual E50417 H8940 C580 A4 Edition 03 2019 ...