Connection Diagrams
This chapter describes the various possibilities to connect the device to the medium-voltage system.
Fault Passage Indicator
The device can be used as a dedicated Fault Passage Indicator (FPI) by using only the 3 current inputs. No
directional fault information is provided in this scheme.
[dw_sfcm-sfpi, 2, en_US]
Figure 7-1
SICAM FCM as Fault Passage Indicator
i
i
NOTE
In this connection scheme, the accuracy of ground-current measurements cannot be guaranteed for
isolated/resonant ground connection.
Ground-Fault Indicator
The device can be used as a dedicated ground-fault indicator by using the ground-current sensor. The
following scheme shows how the device works as a non-directional ground-fault indicator (50 G).
[dw_sfcm_grdfltindi, 2, en_US]
Figure 7-2
SICAM FCM as Ground-Fault Indicator
Fault Detector
The device can be used as a fault detector by providing fault information with directional information. This
requires an additional low-power voltage transformer of 3.25/√3 V or 100/√3 V sensors in the medium-voltage
system or a direct connection to 230 V or when it is connected in the VDS.
For more information about VDS, see chapter
4.1.32 Voltage Measurement via Integrated Voltage-Detecting
.
7.1
Connection Diagrams
7.1 Connection Diagrams
70
SICAM, Feeder Condition Monitor, Manual
E50417-H8940-C580-A4, Edition 03.2019
Содержание SICAM
Страница 8: ...8 SICAM Feeder Condition Monitor Manual E50417 H8940 C580 A4 Edition 03 2019 ...
Страница 11: ...Delivery 1 1 Delivery 12 1 SICAM Feeder Condition Monitor Manual 11 E50417 H8940 C580 A4 Edition 03 2019 ...
Страница 92: ...92 SICAM Feeder Condition Monitor Manual E50417 H8940 C580 A4 Edition 03 2019 ...
Страница 170: ...170 SICAM Feeder Condition Monitor Manual E50417 H8940 C580 A4 Edition 03 2019 ...