Self-Test Mode
In SICAM FCM, the self-test mode feature can be enabled during the commissioning and when required. The
self-test mode is activated via any of the following:
•
HMI
•
RS485/Modbus interface
During the self-test mode, the device changes the values of all Modbus registers and provides an option for
the user to verify the Modbus registers in a sequential order as per the defined-time interval.
In the self-test mode, the correct mapping of all the available Modbus registers (excluding the holding regis-
ters) in a Modbus master and control center can be tested in a very convenient and fast manner. A Modbus
master can read out all the registers and provide them with a time stamp and forward the data to the control
center. In the control center, the received data can be arranged based on the time stamps and should have the
same order as per the following pre-defined self-test mode description.
The self test starts by verifying the hardware in the following sequence:
•
LED Test
•
I>> (forward direction) trip test with DO1 active
•
I> (reverse direction) trip test with DO2 active
•
I
N
> (undetermined direction) trip test with DO1 and DO2 active
After completion of self test, all the coil registers and the discrete input registers (except registers related to
self test) are reset.
The individual Modbus coil registers and the discrete input registers are set for a duration of 5 s and then
reset. After completion of the self test, coil and discrete input registers display the real-time values.
During input-register test, all input registers are set with predefined known values for 10 s. The check using
the time stamp is not necessary as the predefined unique analog values can provide a check of the correct
mapping of the registers. All the input registers display individual measuring values again once the device
exits from the self-test mode. The self-test mode takes 3 min to 4 min to complete.
The following tables display the sequence of the test state and test-state duration.
Modbus Discrete
Input Register
Address
Parameter
Individual Test Value Time Duration
–
LED test
1
10 s
3, 9, 23, 24, 26, 27, 28 I>> trip test
1
10 s
10, 22, 23, 24, 26, 27,
28
I> trip test
1
10 s
4, 11, 12, 29, 30, 31,
32
I
N
> trip test
1
10 s
Table B-17
Bit-Type Data Coil
Modbus Register
Address
Parameter
Individual Test Value Time Duration
1
Test mode
1
Entire duration of self-
test mode
2
Reset display
1
5 s
3
Reserved for future use
–
–
4
Counter reset
1
5 s
5
DO 1
1
5 s
6
DO 2
1
5 s
7
Clear data available status
1
5 s
8
Clear events database
1
5 s
B.9
Modbus Registers
B.9 Self-Test Mode
156
SICAM, Feeder Condition Monitor, Manual
E50417-H8940-C580-A4, Edition 03.2019
Содержание SICAM
Страница 8: ...8 SICAM Feeder Condition Monitor Manual E50417 H8940 C580 A4 Edition 03 2019 ...
Страница 11: ...Delivery 1 1 Delivery 12 1 SICAM Feeder Condition Monitor Manual 11 E50417 H8940 C580 A4 Edition 03 2019 ...
Страница 92: ...92 SICAM Feeder Condition Monitor Manual E50417 H8940 C580 A4 Edition 03 2019 ...
Страница 170: ...170 SICAM Feeder Condition Monitor Manual E50417 H8940 C580 A4 Edition 03 2019 ...