Register-Type Data – Analog Input Registers
Last Reset Type
(Address 1) This register contains the last reset type.
Bit
15
14
13
12
11
10
9
8
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit
7
6
5
4
3
2
1
0
Not used
Not used
Not used
Auto (self)
reset
Modbus
reset
User inter-
face reset
BI reset
Not used
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format
16-bit unsigned integer
Unit
–
Range
–
Last Reset Time (Milliseconds)
(Address 2) This register contains the last reset time in milliseconds.
Bit
15
14
13
12
11
10
9
8
Milliseconds
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit
7
6
5
4
3
2
1
0
Milliseconds
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format
16-bit unsigned integer
Unit
ms
Range
0 to 59999
Last Reset Time (Hours and Minutes)
(Address 3) This register contains the last reset time in hours and minutes.
Bit
15
14
13
12
11
10
9
8
Hours
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit
7
6
5
4
3
2
1
0
Minutes
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format
8-bit unsigned integer
Unit
h
Range
0 to 23
Format
8-bit unsigned integer
Unit
min
Range
0 to 59
Last Reset Time (Month and Date)
(Address 4) This register contains the last reset time in month and date.
B.6
Modbus Registers
B.6 Register-Type Data – Analog Input Registers
144
SICAM, Feeder Condition Monitor, Manual
E50417-H8940-C580-A4, Edition 03.2019
Содержание SICAM
Страница 8: ...8 SICAM Feeder Condition Monitor Manual E50417 H8940 C580 A4 Edition 03 2019 ...
Страница 11: ...Delivery 1 1 Delivery 12 1 SICAM Feeder Condition Monitor Manual 11 E50417 H8940 C580 A4 Edition 03 2019 ...
Страница 92: ...92 SICAM Feeder Condition Monitor Manual E50417 H8940 C580 A4 Edition 03 2019 ...
Страница 170: ...170 SICAM Feeder Condition Monitor Manual E50417 H8940 C580 A4 Edition 03 2019 ...