[dw_sfcmpassmenuaccess, 1, en_US]
Figure 4-25
Password Menu Access
The password can be reset to the default password 1111 by resetting the password in the Modbus register.
Menu navigation is not allowed after 10 wrong attempts. After 10 wrong attempts, reset the password to the
default value. The password cannot be reset through the HMI.
After entering the correct password, you can access the parameters menu. If no key has been pressed during
30 minutes, the parameter menu is closed and the home screen is displayed.
In the battery mode, changing the password is not allowed.
i
i
NOTE
The password has 4 digits. Each digit ranges from 0 to 9. The password 0000 is invalid.
i
i
NOTE
By default, the password protection is disabled.
Device Alerts
The device can detect and indicate overvoltage alarms and warnings, undervoltage alarms and warnings, and
overcurrent alarms and warnings when it is in service. The device alerts are communicated via Modbus and
displayed on the user interface. The alerts reset automatically when the current/voltage falls below the
threshold levels again or exceeds them again in case of an undervoltage.
Undervoltage Alarm and Undervoltage Warning
The undervoltage alerts are enabled when the system voltage falls below the user-defined setting (V
min
Alarm/V
min
Warning). The threshold is defined in percentage of rated primary voltage. For more information
about the undervoltage alarm and undervoltage warning, see
and refer to the Fault Parameters >
Undervoltage Warning and Undervoltage Alarm menu.
Overvoltage Alarm and Overvoltage Warning
The overvoltage alerts are enabled when the system voltage exceeds the user-defined settings (V
max
Alarm/
V
max
Warning). The threshold is defined in percentage of rated primary voltage. For more information about
the overvoltage alarm and overvoltage warning, see
and refer to the Fault Parameters > Over-
voltage Warning and Overvoltage Alarm menu.
4.1.37
Device Functions
4.1 Description
SICAM, Feeder Condition Monitor, Manual
57
E50417-H8940-C580-A4, Edition 03.2019
Содержание SICAM
Страница 8: ...8 SICAM Feeder Condition Monitor Manual E50417 H8940 C580 A4 Edition 03 2019 ...
Страница 11: ...Delivery 1 1 Delivery 12 1 SICAM Feeder Condition Monitor Manual 11 E50417 H8940 C580 A4 Edition 03 2019 ...
Страница 92: ...92 SICAM Feeder Condition Monitor Manual E50417 H8940 C580 A4 Edition 03 2019 ...
Страница 170: ...170 SICAM Feeder Condition Monitor Manual E50417 H8940 C580 A4 Edition 03 2019 ...