Address Min/Max Value Parameters
Unit
Type
1055
0 to 65535
Boot-loader major and maintenance version
number
–
uInt16
1056
0 to 65535
Boot-loader firmware and build version
number
–
uInt16
1057
0 to 65535
Ground-fault status register
–
uInt16
1058
0 to 65535
Phase current I
1
1/10 A
uInt16
1059
0 to 65535
Phase current I
2
1/10 A
uInt16
1060
0 to 65535
Phase current I
3
1/10 A
uInt16
1061
0 to 65535
Ground current I
N
1/10 A
uInt16
For more information about register-type data - analog input registers, see
B.6 Register-Type Data – Analog
.
Table B-7
Analog Input Registers
Address Min/Max Value Parameters
Unit
Type
1
–
Last reset type
–
uInt16
2
0 to 59999
Last reset time (milliseconds)
ms
uInt16
3
0 to 23
0 to 59
Last reset time (hours and minutes)
h and min
uInt16
4
1 to 12
1 to 31
Last reset time (month and date)
month and date
uInt16
5
12 to 99
Last reset time (year)
year
uInt16
6
–
Overvoltage alarm type
–
uInt16
7
–
Overvoltage alarm time (milliseconds)
ms
uInt16
8
–
Overvoltage alarm time (hours and
minutes)
h and min
uInt16
9
–
Overvoltage alarm time (month and date)
month and date
uInt16
10
–
Overvoltage alarm time (year)
year
uInt16
11
–
Overvoltage warning type
–
uInt16
12
–
Overvoltage warning time (milliseconds)
ms
uInt16
13
–
Overvoltage warning time (hours and
minutes)
h and min
uInt16
14
–
Overvoltage warning time (month and date) month and date
uInt16
15
–
Overvoltage warning time (year)
year
uInt16
16
–
Undervoltage alarm type
–
uInt16
17
–
Undervoltage alarm time (milliseconds)
ms
uInt16
18
–
Undervoltage alarm time (hours and
minutes)
h and min
uInt16
19
–
Undervoltage alarm time (month and date) month and date
uInt16
20
–
Undervoltage alarm time (year)
year
uInt16
21
–
Undervoltage warning type
–
uInt16
22
–
Undervoltage warning time (milliseconds)
ms
uInt16
23
–
Undervoltage warning time (hours and
minutes)
h and min
uInt16
24
–
Undervoltage warning time (month and
date)
month and date
uInt16
25
–
Undervoltage warning time (year)
year
uInt16
26
–
Overcurrent alarm type
–
uInt16
Modbus Registers
B.2 Implementation of the Modbus Protocol
SICAM, Feeder Condition Monitor, Manual
103
E50417-H8940-C580-A4, Edition 03.2019
Содержание SICAM
Страница 8: ...8 SICAM Feeder Condition Monitor Manual E50417 H8940 C580 A4 Edition 03 2019 ...
Страница 11: ...Delivery 1 1 Delivery 12 1 SICAM Feeder Condition Monitor Manual 11 E50417 H8940 C580 A4 Edition 03 2019 ...
Страница 92: ...92 SICAM Feeder Condition Monitor Manual E50417 H8940 C580 A4 Edition 03 2019 ...
Страница 170: ...170 SICAM Feeder Condition Monitor Manual E50417 H8940 C580 A4 Edition 03 2019 ...