Operational Indications
Operational Indications
Indication
Description
Notes
Device OK
The device startup was successful. Indication ON: Device ready
Battery Failure
Battery voltage < 2.7 V or no
battery inserted
Indication ON: Battery failure
Time Synchronization
Error
Error during the time synchroniza-
tion from the NTP server or
fieldbus
Indication OFF: At least 1 time message was received
during the set timer (Error indication after). The time
stamp is set when the first valid time information or time
synchronization is received.
Indication ON: No time message was received during the
set timer (Error indication after).
The time stamp is set after the Error indication after timer
has expired and no synchronization message was received.
Parameter range: see chapter
.
Error sources with NTP or fieldbus: Error indication after
timer expires and no synchronization message was received
Error during internal time synchro-
nization
Indication ON: RTC time invalid (during device start in case
of battery failure)
Indication OFF: After setting the clock via HTML
During battery failure at device startup
Default IP Address
The device has started with a
default IP address after pressing
the push-button for more than 3 s
during operation.
Indication ON: The push-button was pressed and default IP
is set in the device.
Primary NTP Server
Error
Faulty or no response from the
primary NTP server
Indication ON: Error
Indication OFF: Valid time messages have been received for
a configured period.
Only for time synchronization via Ethernet NTP
Secondary NTP Server
Error
Faulty or no response from the
secondary NTP server
Indication ON: Error
Indication OFF: Valid time messages have been received for
a configured period.
Only for time synchronization via Ethernet NTP
Daylight Saving Time
Switching between daylight saving
time/standard time
Indication ON: Daylight saving time
Indication OFF: Standard time
Ethernet Link Error
Ethernet connection error
Indication ON: Error
Indication OFF: Ethernet link recognized
Modbus TCP OK
(Modbus TCP Server)
At least 1 Modbus TCP server
connection has received Modbus
messages.
Indication ON: At least 1 Modbus message was received
during the set communication supervision time. The time
stamp is set when the first valid message is received.
Indication OFF: No Modbus message was received during
the set communication supervision time
IEC 61850 Communi-
cation OK
Communication via protocol IEC
61850 is correct.
Indication ON: At least one message was received during
the set monitoring time. The time stamp is set when the
first valid message is received.
Indication OFF: No message was received during the set
monitoring time.
13.1
13.1.1
Operational Indications and Operating Parameters
13.1 Operational Indications
260
SICAM, SICAM P850/P855 7KG85X, Manual
E50417-H1040-C482-A9, Edition 03.2022
Содержание SICAM 7KG85X
Страница 1: ...SICAM 7KG85X Power Monitoring Device SICAM P850 Power Quality Device SICAM P855 www siemens com SICAM ...
Страница 7: ...6 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Страница 29: ...28 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Страница 99: ...98 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Страница 233: ...232 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Страница 259: ...258 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Страница 277: ...276 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...
Страница 281: ...280 SICAM SICAM P850 P855 7KG85X Manual E50417 H1040 C482 A9 Edition 03 2022 ...