Application planning
4.2 Power supply, grounding, and connection
Air circuit breaker 3WL10
118
Manual, 11/2017, L1V30499596002-01
Means of connection, cables
A
[mm]
∅
[mm]
A ∅
[mm
2
]
Connections of the fixed breaker version
Circular conductor terminal,
adapter 4x240
30
21.5
120 to 240
The following applies to connecting bars to horizontally / vertically orientable rear terminals
for main circuit connection:
Rated uninterrupted current I
u
[A]
Busbar dimensions
Horizontally oriented
rear terminals
Vertically oriented
rear terminals
630
2 x 40 x 5
●
●
800
2 x 50 x 5
●
●
1000
2 x 50 x 10
●
—
2 x 50 x 8
—
●
1250
2 x 50 x 10
●
—
2 x 50 x 8
—
●
Grounding
The fixed circuit breaker does not require grounding.
For the withdrawable breaker, two alternatives are possible to achieve continuity and
equipotentiality of the grounding between the circuit breaker and the protection circuit of the
switchboard:
●
Connection of the guide frame to the protection circuit with a cable in accordance with
IEC 61439-1, Section 10.5.2
●
If a conductive connection between the guide frame and the grounding of the switchboard
is ensured via the metal base (floor mounting) or the metal wall (wall mounting) of the
switchboard panel, no additional grounding is required. This means there must be no
insulation material between the circuit breaker and the grounded metal of the switchboard
panel.
Содержание SENTRON 3WL10
Страница 1: ......
Страница 2: ......
Страница 8: ...Table of contents Air circuit breaker 3WL10 6 Manual 11 2017 L1V30499596002 01 ...
Страница 14: ...Introduction 1 3 Safety instructions Air circuit breaker 3WL10 12 Manual 11 2017 L1V30499596002 01 ...
Страница 21: ...Description 2 2 Possible uses and portfolio Air circuit breaker 3WL10 Manual 11 2017 L1V30499596002 01 19 ...
Страница 108: ...Accessories 3 5 Breaker Data Adapters and test devices Air circuit breaker 3WL10 106 Manual 11 2017 L1V30499596002 01 ...
Страница 128: ...Application planning 4 3 Communication planning Air circuit breaker 3WL10 126 Manual 11 2017 L1V30499596002 01 ...
Страница 152: ...Connection and commissioning 5 4 Commissioning Air circuit breaker 3WL10 150 Manual 11 2017 L1V30499596002 01 ...
Страница 170: ...Operation 6 3 Troubleshooting Air circuit breaker 3WL10 168 Manual 11 2017 L1V30499596002 01 ...
Страница 180: ...Technical specifications Air circuit breaker 3WL10 178 Manual 11 2017 L1V30499596002 01 ...
Страница 198: ...Dimension drawings 9 2 Withdrawable breaker Air circuit breaker 3WL10 196 Manual 11 2017 L1V30499596002 01 ...
Страница 199: ...Air circuit breaker 3WL10 Manual 11 2017 L1V30499596002 01 197 Circuit diagrams 10 ...
Страница 212: ...Circuit diagrams Air circuit breaker 3WL10 210 Manual 11 2017 L1V30499596002 01 ...
Страница 230: ...List of abbreviations C 1 Table of abbreviations Air circuit breaker 3WL10 228 Manual 11 2017 L1V30499596002 01 ...
Страница 233: ......
Страница 234: ......