2.4 Electronic trip unit ETU
Air circuit breaker 3WL10
Manual, 11/2017, L1V30499596002-01
59
Protection functions of the ETU
ETU650 LSI
ETU660 LSIG
G direct
GF direct: Ground-fault protection direct
measurement
—
●
Default set: Not installed
Protection function can be selected
•
R
c
- residual-current protection
(with summation current transformer)
•
G
ret
- ground-fault return protection
(transformer in the star point)
—
Ground return CT; Rc CT;
necessary
Rc - residual-current protection
(with summation current transformer)
—
●
Alternative to GF and G_ret
Default value: OFF
Possible with current sensor
Rc & MF advanced
Setting range operating value residual
current I
∆
n
—
3; 5; 7; 10; 20; 30 A
Default value: OFF
Possible with current sensor
Rc & MF advanced
Setting range for delay time t
∆
n
—
0.06; 0.1; 0.2; 0.3; 0.4; 0.5;
0.8 s
Gret ground-fault return protection
(ground return - transformer in the star point)
—
●
Alternative to GF and Rc
Design of G
ret
transformer
(ground fault return CT, I
CT_rating
)
—
100; 250 A
Default value: 100 A
Setting range operating value ground fault
return I
g_ret
= I
CT_rating
x ...
—
0.1 to 1 x I
CT_rating
(in steps of
0.001)
Default value: 0.1
Setting range of delay time t
g_ret
(fixed) t=k
—
0.1 to 1 s (in steps of 0.05)
Default value: 0.1s
Setting range for delay time t
g_ret
at I²t
(reference point 4 x I
n
)
—
0.1s to 1s (in steps of 0.05)
Ground-fault return protection pre-alarm
—
50 to 90 % x I
r
(in steps of
1%)
Default value: 90 %
Switchover to alternative operating values with
ground-fault current during the switch-on phase
(inrush adaptation) for tripping characteristic t=k
(fixed) possible
—
●
Default value: OFF
Setting range of the switch-on phase
(inrush adaptation)
—
0.1 to 30 s (in steps of 0.01)
Default value: 0.1
Setting range I
g
= I
n
x … during the switch-on
phase (inrush adaptation)
—
0.1 to 1 (in steps of 0.01)
Default value: 1
Содержание SENTRON 3WL10
Страница 1: ......
Страница 2: ......
Страница 8: ...Table of contents Air circuit breaker 3WL10 6 Manual 11 2017 L1V30499596002 01 ...
Страница 14: ...Introduction 1 3 Safety instructions Air circuit breaker 3WL10 12 Manual 11 2017 L1V30499596002 01 ...
Страница 21: ...Description 2 2 Possible uses and portfolio Air circuit breaker 3WL10 Manual 11 2017 L1V30499596002 01 19 ...
Страница 108: ...Accessories 3 5 Breaker Data Adapters and test devices Air circuit breaker 3WL10 106 Manual 11 2017 L1V30499596002 01 ...
Страница 128: ...Application planning 4 3 Communication planning Air circuit breaker 3WL10 126 Manual 11 2017 L1V30499596002 01 ...
Страница 152: ...Connection and commissioning 5 4 Commissioning Air circuit breaker 3WL10 150 Manual 11 2017 L1V30499596002 01 ...
Страница 170: ...Operation 6 3 Troubleshooting Air circuit breaker 3WL10 168 Manual 11 2017 L1V30499596002 01 ...
Страница 180: ...Technical specifications Air circuit breaker 3WL10 178 Manual 11 2017 L1V30499596002 01 ...
Страница 198: ...Dimension drawings 9 2 Withdrawable breaker Air circuit breaker 3WL10 196 Manual 11 2017 L1V30499596002 01 ...
Страница 199: ...Air circuit breaker 3WL10 Manual 11 2017 L1V30499596002 01 197 Circuit diagrams 10 ...
Страница 212: ...Circuit diagrams Air circuit breaker 3WL10 210 Manual 11 2017 L1V30499596002 01 ...
Страница 230: ...List of abbreviations C 1 Table of abbreviations Air circuit breaker 3WL10 228 Manual 11 2017 L1V30499596002 01 ...
Страница 233: ......
Страница 234: ......