Operation
6.1 Operation
Air circuit breaker 3WL10
154
Manual, 11/2017, L1V30499596002-01
Opening and closing via remote access
Remote access is possible in two ways:
●
Via the communication system, the precondition being a COM connection and the
COM actuator module
●
Via direct electrical signals at the auxiliary conductor terminal system
The circuit breaker can be closed and opened by remote access. For this purpose, the
optional closing coils (CC) / shunt releases (ST) must be installed. You will find information
on these coils in Section Accessories for circuit breaker (Page 75).
Closing/opening the circuit breaker via the communication system
1.
Charge the storage spring if it is not already charged.
It is advisable to use the accessory spring charging motor (MO) so that the spring energy
store can be charged via the communication system, too.
2.
Transmit a closing/opening command via the COM connection and control system.
Closing/opening the circuit breaker via the auxiliary conductor terminal system
1.
Charge the spring energy store if it is not already charged.
2.
Transmit the closing/opening command to the closing coil (CC) or the shunt release (ST).
Содержание SENTRON 3WL10
Страница 1: ......
Страница 2: ......
Страница 8: ...Table of contents Air circuit breaker 3WL10 6 Manual 11 2017 L1V30499596002 01 ...
Страница 14: ...Introduction 1 3 Safety instructions Air circuit breaker 3WL10 12 Manual 11 2017 L1V30499596002 01 ...
Страница 21: ...Description 2 2 Possible uses and portfolio Air circuit breaker 3WL10 Manual 11 2017 L1V30499596002 01 19 ...
Страница 108: ...Accessories 3 5 Breaker Data Adapters and test devices Air circuit breaker 3WL10 106 Manual 11 2017 L1V30499596002 01 ...
Страница 128: ...Application planning 4 3 Communication planning Air circuit breaker 3WL10 126 Manual 11 2017 L1V30499596002 01 ...
Страница 152: ...Connection and commissioning 5 4 Commissioning Air circuit breaker 3WL10 150 Manual 11 2017 L1V30499596002 01 ...
Страница 170: ...Operation 6 3 Troubleshooting Air circuit breaker 3WL10 168 Manual 11 2017 L1V30499596002 01 ...
Страница 180: ...Technical specifications Air circuit breaker 3WL10 178 Manual 11 2017 L1V30499596002 01 ...
Страница 198: ...Dimension drawings 9 2 Withdrawable breaker Air circuit breaker 3WL10 196 Manual 11 2017 L1V30499596002 01 ...
Страница 199: ...Air circuit breaker 3WL10 Manual 11 2017 L1V30499596002 01 197 Circuit diagrams 10 ...
Страница 212: ...Circuit diagrams Air circuit breaker 3WL10 210 Manual 11 2017 L1V30499596002 01 ...
Страница 230: ...List of abbreviations C 1 Table of abbreviations Air circuit breaker 3WL10 228 Manual 11 2017 L1V30499596002 01 ...
Страница 233: ......
Страница 234: ......