8.5 Binary
input
binF
This setting decides on the use of the binary input.
Reference!
See chapter 5.4
Predefined setpoint.
ConF
binF
Parameter Value/
selection
Description
0 No
function
1 Setpoint
changeover
2 Setpoint
shift
Binary input
bin1
Binary inputs
4
Changeover of operating mode
Burner modulating:
Contacts D1 and DG open
Burner 2-stage:
Contacts D1 and DG closed
46/68
20089337