9.2 Checking the controller parameters
Optimum adjustment of the controller to the controlled system can be checked by
recording a startup sequence with the control loop closed. The following diagrams
indicate possible incorrect adjustments, and their correction.
The response to a setpoint change is shown here for a 3rd order controlled system for
a PID controller. The method used for adjusting the controller parameters can,
however, also be applied to other controlled systems. A suitable value for
dt
is
rt
/
4
.
Pb
too small
Pb
too large
t
x
w
7865d17/1099
Figure 27:
Pb
too small
t
x
w
7865d15/1099
Figure 28:
Pb
too large
rt
,
dt
too small
rt
,
dt
too large
t
x
w
7865d16/1099
Figure 29:
rt
,
dt
too small
t
x
w
7865d14/1099
Figure 30:
rt
,
dt
too large
Optimum adjustment
t
x
w
7865d18/1099
Figure 31: Optimum adjustment
Example
50/68
20089337
Содержание RWF 50.2
Страница 2: ...20089337 Translation of the original instructions ...
Страница 4: ...2 68 20089337 ...
Страница 6: ...4 68 20089337 ...
Страница 14: ...1 4 Block structure Only RWF50 3 Only RWF50 2 Air damper control Figure 1 Block structure 12 68 20089337 ...
Страница 62: ...60 68 20089337 ...
Страница 66: ...64 68 20089337 ...
Страница 69: ......
Страница 70: ......
Страница 71: ......