16 Function block D.h.w. heating
27.05.2004
16
Function block D.h.w. heating
This function block contains all
settings
for the general d.h.w. functions. Not included
are the following parameters:
•
The setpoints of the d.h.w. temperature. These setpoints can be adjusted by the end-
user on operating lines 41 and 42
•
The parameters for the control of the actuators
•
The parameters on the locking function level
These parameters are contained in separate function blocks.
The details of the different types of d.h.w. heating (with coil type storage tank, directly
via heat exchanger or with stratification storage tank) are described in the following
sections.
16.1 Operating
lines
Line Function, parameter
Unit
Factory
setting
Range
101
Release of d.h.w. heating
0
0…2
102
Release of circulating pump
1
0…2
103
Switching differential of the d.h.w. temperature
K
5
1…20
104
Legionella function
6
--- / 1…7, 1-7
105
Setpoint of legionella function
°C
65
60…95
106
D.h.w. priority
4
0…4
107
Overrun time of intermediate circuit pump
min
4
0…40
108
Extra overrun time of charging pump
min
1'00
0'10…40'00
109
Maximum time of d.h.w. heating
min
150
--- / 5…250
110
Protection against discharging during d.h.w. pump overrun
0
0 / 1
16.2 Release of d.h.w. heating
The release of d.h.w. heating can be selected on operating line 101, depending on the
type of plant:
•
For the release of d.h.w. heating, there are 3 choices available:
Setting Release
0
D.h.w. heating is always released (24-hour program)
1
•
Plant types 1–x, 2–x, 3–x and 8–4:
The release takes place according to the heating circuit program en-
tered on operating lines 6 through 12. In that case, the start of the first
release period is always shifted forward by the time set on operating
line 109 (maximum time)
•
Plant types 0–x, 5–x and 6–x:
The release takes place according to the time program of the control-
lers defined on operating line 125 (refer to chapter 20 “Function block
Assignment of d.h.w. heating”)
•
Plant type no. 7–2:
The release takes place based on
both
criteria
2
The release takes place according to the d.h.w. program entered on
operating lines 17 through 23
Release means that d.h.w. heating takes place at the nominal setpoint (operating line
41).
At the end of a release phase, the reduced d.h.w. temperature setpoint applies (op-
erating line 42).
•
In the case of direct d.h.w. heating via heat exchanger, operating line 109 is inactive.
The release of d.h.w. heating is not connected to the operating level of space heating.