92/130
Siemens Building Technologies
Basic Documentation RVD230
CE1P2383en
HVAC Products
26 Function block Test and display
27.05.2004
26
Function block Test and display
26.1 Operating
lines
Line
Function, parameter
Unit
Factory setting
Range
161
Sensor test
0
0…11
162
Display of setpoint
0
0…11
163
Relay test
0
0…10
164
Speed of speed-controlled pump
Display function
165
Display of digital inputs
Display function
169
Display of active limitations
Display function
170
Software version
Display function
26.2 Sensor
test
The sensor test includes the temperature acquired with each sensor and the voltage
present at the analog input. Interrogation is made with the setting buttons
and
.
To identify the acquired variable, a code is used.
The numbers on the display have the following meaning:
--.- = open-circuit / no sensor connected to input B9
oo.o = short-circuit at input B9
--- = open-circuit / no sensor present
ooo = short-circuit at the other inputs
Code Input Acquired
variable,
measured
value
0 B9
Weather
(outside
temperature)
1
B1
Heating circuit flow temperature
2 B3
D.h.w.
3 A6
Room
unit
5 B7
Return
temperature
6 B71
Return
temperature
7 B72
Return
temperature
8 B31
Storage
tanks
9 B32
Storage
tanks
10
B12
Heating circuit or d.h.w. flow
11
U1
DC 0…10 V / 0…130 °C
26.3 Setpoint test
The setpoint test includes the display of the setpoint assigned to each sensor. Interro-
gation is made with the setting buttons
and
. To identify the acquired variable, a
code is used.
--- means: No setpoint available
Code
Input
Setpoint of the …
0 B9
Composite
outside
temperature
1
B1
Heating circuit flow temperature
2
B3
D.h.w. flow temperature
3 A6
Room
temperature
5 B7
Return
temperature
6 B71
Return
temperature
7 B72
Return
temperature
8 B31
Storage
tanks
9 B32
Storage
tanks
10
B12
Heating circuit or d.h.w. flow
11 –
(Not
available)