85/130
Siemens Building Technologies
Basic Documentation RVD230
CE1P2383en
HVAC Products
23 Function block Device functions
27.05.2004
23
Function block Device functions
23.1 Operating
lines
Line
Function, parameter
Unit
Factory setting
Range
141
Pulse lock
1
0 / 1
142
Frost protection for the plant
1
0 / 1
143
Flow alarm
h
--:--
--:-- / 0: 10…10:00
144
Winter- / summertime changeover
25.03.
01.01. … 31.12
145
Summer- / wintertime changeover
25.10.
01.01. … 31.12
23.2 Actuator pulse lock
This function acts on all 3-position actuators controlled by the RVD230.
If, during a total period of time that equals 5 times the running time, an actuator has
received opening or closing pulses, additional closing pulses in the same direction will
be suppressed by the controller.
For safety reasons, the controller delivers a one-minute closing pulse in the appropriate
direction to the controller at 10-minute intervals.
A pulse in the opposite direction negates the pulse lock.
This function acts on all actuators used in the plant and is intended to reduce the wear
on the relay contacts and to extend the life of the actuators. It can be deactivated on
operating line 141 (entry of 0).
23.3 Frost protection for the plant
23.3.1 Principle
Frost protection for the plant protects the plant against freeze-ups by activating the
heating circuit pump. For this purpose, both the controller and the heat source must be
ready to operate (mains voltage present).
Frost protection for the plant is possible with or without outside sensor. The switching
differential is 1 K (fixed value).
Frost protection is always active, also
•
when the control is switched off (standby )
•
during quick setback
•
during OFF periods by the ECO function
If required, frost protection for the plant can be deactivated (setting on operating line
142 = 0).
In addition to frost protection for the plant through activation of the heating circuit pump,
frost protection for the heating circuit flow is active.
23.3.2 Mode of operation with outside sensor
Frost protection for the plant operates in 2 stages:
1. If the outside temperature falls below 1.5 °C, the heating circuit pump will be acti-
vated for 10 minutes at 6-hour intervals.
2. If the outside temperature falls below –5 °C, the heating circuit pump will be acti-
vated and runs continuously.
When active, the respective frost protection stage will be switched off when the outside
temperature has exceeded the limit value by 1 K.