KNX bus communications
CE1P3127en
Building Technologies
Communication via zone addresses
2013-04-08
RMS705B (device 1) contains the air quality value of an air quality sensor. This
value is transmitted as transmission object via an analog output and further
processed by a RMS705B (device 2).
The following transmission and reception zone is engineered for our example:
RMS705B, device 1
RMS705B, device 2
Value
Terminal Transmission
zone Terminal Reception
zone
N.Y1
1
N.X1
1
Air quality
mean value
= Transmit
= Receive
The following is configured in RMS705B, device 1:
Main menu > Commissioning > Communication > LTE transmission zones >
Operating line
Range
Factory setting
N.Y1
1
The following is configured in RMS705B, device 2:
Main menu > Commissioning > Extra configuration > Input identifier >
Operating line
Range
Factory setting
N.X1
ppm
Main menu > Commissioning > Communication > LTE reception zones >
Operating line
Range
Factory setting
N.X1
1
Example 1
Data exchange concept
Configuration
Device 1
Device 2