KNX bus communications
CE1P3127en
Building Technologies
Basic communication settings
2013-04-08
6.1.4
Remote reset of fault
The "Remote reset of fault" function is used to reset Synco 700 RM… controller
faults transmitted over the KNX bus requiring acknowledgement and reset to be
acknowledged (and reset if "Remote reset of fault: Yes") with the OCI700.1 service
tool, the RMZ792 bus operator unit, the OZW772 web server, and the OZW775
central communication unit.
Main menu > Commissioning > Communication > Basic settings
Basic settings
Dec bus power supp: On
Clock time op: Slave
Rem set clock slave: Yes
Remote reset fault: Yes
Remote reset of faults for the RM… controllers
Default value.
No
Setting values
No/Yes
Apart from the RMH780 heating controller, all RM… controllers (including the
RMH760B heating controller) incorporate the "Remote reset of faults" function.
RM… controllers
Note