KNX bus communications
CE1P3127en
Building Technologies
Appendix
2013-04-08
9.2.2
Changeover via analog input
The outside temperature sensor is wired to universal input "x" (configured as
analog input) of the "H/C changeover" function block in controller 1 (RMU7x0B).
The release relay in controller 1 acts on heating/refrigeration generation. The
heating/cooling changeover signal acts on all controllers (here, controllers 1 and 2)
in the same heating/refrigeration distribution zone.
If an analog signal is the source of the H/C changeover, two limit values must be
selected for changeover. For further information see basic documentation, manual
P3150.
1
M
T
1
KNX
2
M
2
T
T
2
S1
S1
S1
S2
S2
x
S2
S3
Q
Y
d
1
2
3
x
Kältebedarf
Q
Y
d
S4
S4
S4
S5
1
2
3
x
Q
23
1
S1
S1
S1
S2
S2
x
S2
S3
Q
Y
d
1
2
3
x
Kältebedarf
Q
Y
d
S4
S4
S4
S5
1
2
3
x
Q
23
T
AI
Htg/ClgCoil 1
Htg/ClgCoil 2
3
1
2
7
S
0
4
e
n
Flow
Return
H/C changeover signal
Heat/refrig distribution zone 1
H/C changeover
Heat demand
Supervision
Controller
Controller
Supervision
Refrig demand
H/C changeover
Heat demand
Supervision
Controller
Controller
Supervision
Refrig demand
Changeover source
analog input AI
Note