KNX bus communications
CE1P3127en
Building Technologies
Appendix
2013-04-08
QAW740
RMH...
RMH...
3
1
2
7
Z
2
8
e
n
Geogr zone: 1
Room unit
Geogr zone: 1
Operating mode
Geogr zone: 1
Heating circuit 1, master
Operating mode
Heating circuit 2, slave
Room control combination
Master
Transmits room setpoint and operating mode.
Room control combination
Slave, external setpoint
Receives room setpoint and operating mode.
Room control combination
Slave, internal setpoint
Retains its own room setpoint as valid, but adopts the
operating mode from the master.
Room control combinations featuring multiple ventilation controllers
When a space is controlled by several ventilation controllers, e.g. two RMU7x0B
controllers (they must be RMU7x0B controllers) controlling the temperature in a
warehouse, the controllers can exchange information such as room temperature,
operating mode, and setpoint over the KNX bus.
With this room control combination, one ventilation controller must be set as the
master and all the others as slaves.
QAW740
RMU...
RMU...
3
1
2
7
Z
4
9
d
e
Geogr zone = 2
Room operating mode
Geogr zone = 2
Ventilation 1
Room control comb. =
Master
Room control comb. =
Slave ext. setpoints
Room unit
Geogr zone = 2
Room operating mode
Ventilation 2
Within the room control combination, the slave ventilation controller operates with
the same operating mode as the master.
The slave controllers can use either the same setpoints as the master, or individual
setpoints.
Zone addressing
Set room control
combination
Application example 2
Note
Zone addressing
Slave ventilation
controller settings