Commissioning
28.08.2012
2.9 Final
steps
2.9.1
Check faults
The fault indicator displays the plant state.
No faults may be pending after commissioning. Additional information on faults
is available in Section 3.3.
The fault indicator remains green as long as no fault is pending.
The fault indicator changes to red for faults.
The most severe plant faults are displayed:
•
Device name
•
Fault text
2.9.2
Final steps on web server
The final function checks are conducted on the web server, the cover is mounted
and the LEDs checked.
On display and operating elements, see Section 1.2.
Procedure:
1.
Unplug USB cable.
2.
Switch off message suppression:
– Remove the cover
– Message suppression switch (
8
) must be on "Off"
.
3.
Mount terminal cover.
4.
Press Remote (
6
) button for more than 6 seconds.
– The web server sends a system report to the defined message receivers.
– Fault LED (
4
) displays (flashing) error in establishing communications.
5.
On LED must be green.
6.
Fault LED must be dark.
Fault indication
Note
No fault
Fault
Final tasks
Note