26 / 116
Siemens
Web server OZW672... V4.0
CE1C5712en
Building Technologies
Commissioning
28.08.2012
Path: Home > 0.5 OZW672… > > Settings > Communication > E-mail
•
Enter these settings if the web server is to send an e-mail for a fault.
•
Additional information on email settings is available in Section 6.2.
•
Automatically negotiate the securest connection:
TLS mode is selected automatically if the device sending the email and the
email provider supports it.
Data point
Explanation, example
Address mail server
Default val:
smtp.example.com
Setting val:
Max. 46 characters
The provider supplies the IP address or mail
server domain name. Often referred to as the
outgoing mail server or SMTP server instead of
mail server.
—
Port number mail server
Default val: 25
Setting val:
1…65535
Port number 25 is default for the mail server
(and does not normally require change).
—
E-mail address sender
Default val:
[email protected]
Setting value:
Max. 46 characters
The setting corresponds to the e-mail address
of the web server.
The email address is displayed in the "From"
field of each email.
—
Authentification mail
server
Default val:
No
Setting val:
No/Yes
Select
Yes
for mail server access with authen-
tication.
In this case, user name and password (data
points below) are required.
—
User name
Default val: (Blank)
Setting val:
Max. 46 char.
User name and password help authenticate
each e-mail via the mail server.
—
Password
Default val:
(Blank)
Setting val:
Max. 46 char.
Password and user name help authenticate
each email via the mail server.
—
Signature line 1..10
Default val:
(Blank)
Setting val:
Max. 46 char.
Signature lines are transmitted with the e-mail.
It identifies the sender, e.g. the plant's Internet
address.
—
Path: Home > 0.5 OZW672… > Settings > Communication > USB
Data point
Explanation, example
UPnP localization
Default val: USB
Setting val:
---, Ethernet, USB
The web server registers its presence in the
network via the Universal Plug and Play
(UPnP) service.
—
Web server registers its existence in the USB network, when
•
"UPnP localization" = "USB" is set
and
•
The connection between PC/laptop and the web server is active via USB.
Notes
USB
UPnP localization