When you change one of the following texts, the status at the web server changes
from "Generated" to "Not updated":
•
Message receiver 1…4
•
Fault input 1…2
•
Text for: No fault
•
Text for: Fault
You can change the following texts without influencing device status:
•
Name (web server).
•
Bus device name.
You must update the device web pages of the web server to apply all text changes
to the menu.
•
You can update device web pages on user levels "Administrator" and "Service".
•
Click [ Update ] on the Service and [ Generate ] on the Administrator level to
start updating (see "Create device web pages").
The following update procedure applies to the Service level:
1.
Select the web server
.
2.
Click [ Update ]
The device web pages are updated
.
Process takes a few minutes
3. Wait
until
Process finished
is displayed.
The device list for the web server display state "Generated".
Update device
websites
Notes