81 / 116
Siemens
Web server OZW672... V4.0
CE1C5712en
Building Technologies
"Energy indicator" function
28.08.2012
The values of the data points "Energy indicator transmitted" and "Reason" are dis-
played after testing until:
•
Another test is triggered manually.
•
The next transmitted e-mail is transmitted as per Transmit time 1 and/or 2.
•
The device supply is switched on and off.
Data point
Function
Test receiver
[ ---, trigger]
"Energy indicator transmitted"
[ ---, Yes, No]
Reason
[ ---, DNS setting, mail server address, mail
server port number, e-mail address recipient,
mail server authentication, network cable]
Manual triggering for test purposes does not trigger a fault message.
If an e-mail with "Energy indicator" of the plant is not transmitted without error,
a fault message is triggered for the corresponding e-mail recipient.
The fault message is reset if:
•
The next transmitted e-mail is transmitted as per Transmit time 1 and/or 2.
•
Manually triggered "Test receiver" is successful.
The diagnostic options are identical to those of other e-mail recipients.
5.5.2
Mail inbox
"Energy indicator
transmitted" and "Reason"
Note
Fault message e-mail
Reset
fault message
Note