27 / 116
Siemens
Web server OZW672... V4.0
CE1C5712en
Building Technologies
Commissioning
28.08.2012
Path: Home > 0.5 OZW672… > Settings > Message receiver > Message receiver
1…4
The settings are made if the web server sends messages via e-mail.
Data point
Explanation, example
Message receiver 1…4
Default val: (Blank)
Setting val:
Max. 20 char.
Customizable text for message recipient. The
designation is displayed in the menu and
transmitted as part of the message.
Notes:
•
Note Section 2.4 "Update device web
pages".
•
Delete the entry to reset to default text.
—
Receiver type
Default val: ---
Setting val:
The following recipient types are available:
---
: No messages to this recipient.
: Message recipient configured for e-
mail messages via Ethernet.
—
Fault priority
Default val: All
Setting val: All,
Only urgent ones
Setting value "
Only urgent ones
" serves as a
filter when sending system reports and fault
status messages.
—
E-mail address
Default val: Max. 46 characters
For E-mail recipient types:
Setting value is recipient email address.
—
Path: Home > 0.5 OZW672… > Settings > System report
Enter these settings if the web server is to regularly send an e-mail for a fault.
Data point
Explanation, example
Signal time
Default val:
06:00 hh:mm
Setting val:
00:00...23:59
(Resol. 00:01).
The setting value corresponds to the time of
day when a system report is sent (time can be
defined).
—
Message cycle
Default val: 1 d (day)
Setting val:
0...255 d
(Resolution: 1 d)
The setting value corresponds to the interval
(in days) at which a system report is sent.
The first system report is delivered after com-
pletion of the first message cycle and then as
per the message cycle. The system report is
disabled when the message cycle =0.
—
Priority
Default val: Urgent
Setting val:
Urgent /
Not
urgent
Filter when sending the system reports.
The setting "
Urgent
" sends the system report
to all active message recipients. The setting
Not urgent
exempts all message recipients
subscribing to "Only urgent ones".
—
Next report
Default val: 0 d (day)
Setting val:
0...255 d
(Resolution: 1 d)
Waiting time to next system report.
—
Message receiver 1…4
Note
System report
Note