28 / 116
Siemens
Web server OZW672... V4.0
CE1C5712en
Building Technologies
Commissioning
28.08.2012
Path: Home > 0.5 OZW672… > Settings > Inputs > Fault input 1…2
Digital inputs D1, D2 help connect potential-free status contacts. They work as fault
inputs.
The following settings show how to configure fault inputs.
Select "Settings > Faults > Local > Fault input 1…2" to define behavior during
faults.
Data point
Explanation, example
Fault input 1…2*
Default val: (Blank)
Setting val:
Max. 20 char.
Customizable text for fault input. The designa-
tion is displayed in the menu and transmitted as
part of the message.
Identical to data point in "Settings > Faults >
Local > Fault input 1…2".
—
Normal position
Default val: Open
Setting val: Open,
Closed
Normal position specifies the contact position
deemed "No fault".
—
Text for: Logic 0*
Default val: 0
Setting val:
Max. 20 charac-
ters
Logic 0: No fault.
Customizable text for fault input status, e.g.
Water pressure normal.
—
Text for: Logic 1*
Default val: 1
Setting val:
Max. 20 char.
Logic 1: Fault.
Customizable text for fault input status, e.g.
Water pressure too low.
—
* Notes:
•
Note Section 2.4, "Update device web pages".
•
Delete the entry to reset to default text.
Path: Home > 0.5 OZW672… > Settings > Faults
The following settings specify behavior in case of faults.
Select "Settings > Inputs > Fault input 1…2" to configure the fault inputs.
Data point
Explanation, example
Message triggering
Default val.: Coming
Setting val:
Coming,
Coming and going
Coming
: A message is triggered when a fault
is received (start of fault).
Coming and going
: A corresponding mes-
sage is triggered at start and end of fault. A
web server fault displays the LED .
—
Fault input 1..2*
Default val.: (Blank)
Setting val:
Max. 20 char.
Customizable text for fault input. The designa-
tion is displayed in the menu and transmitted
as part of the message.
Identical to data point in "Settings > Inputs >
Fault input 1…2".
—
Fault status message
delay mm:ss
Default val.: 00:05.
Setting val: 00:00…59:55
(Resolution
00:05)
The Fault status message delay acts as a filter
for short-term fault events. The time the web
server must wait until a fault becomes active
is set here.
—
Fault input 1...2
Note
Faults