8 / 116
Siemens
Web server OZW672... V4.0
CE1C5712en
Building Technologies
Overview
28.08.2012
1.2
Display and operating elements
Pos
Name
1
On LED, Operation and
"Energy indicator"
2 A
LPB/BSB LED
3 B
No function
4
Fault LED
5 (LED)
No function
6
Remote button
7
Service button
8
Message suppression switch
9
No function
•
Dark
No power.
•
Steady red
Web server starts operating system.
•
Flashing red
Web server starts application.
•
Steady green
Web server operational, "Energy indicator" = "Green leaf".
•
Steady orange
Web server operational, "Energy indicator" = "Orange leaf".
•
Dark
No bus power.
•
Lit
LPB/BSB operational.
•
Flashing
Communication on LPB/BSB.
No
function.
•
Dark
No fault (normal operating state).
•
Lit
Fault exists.
No
function.
•
Long (> 6 s)
Sends system report to fault e-mail recipients
(not to "Energy indicator" recipients)
•
Long (> 6 s)
See "Button combinations".
•
Long (> 6 s)
Simultaneously press and restores default factory
settings.
Note : All configuration data and settings are reset. The
device list, uploaded files, and all unsent messages are
deleted. History data is not deleted.
•
Position "On" Messages cannot be sent.
•
Position "Off" Message sending allowed.
No
function.
Overview
LED displays
1
(red/ green/orange)
2
LPB/BSB A
(green)
3
(LED) B
4
Faults (red)
5
(LED)
Operating buttons
6
Remote
7
Service
Button combinations
and
Switch
8
Message inhibition
9
(DIP switches)