32
BndWid
ASG
Band width voltage (as voltage or percent of nominal voltage,
FPF presumed)
0
CtIDITmms
ING
Control intentional time delay (FPF presumed)
0
LDCR
ASG
Line drop voltage due to line resistance component
0
LDCX
ASG
Line drop voltage due to line reactance component
0
BlkLV
ASG
Control voltage below which auto lower commands blocked
0
BIkRV
ASG
Control voltage above which auto raise commands blocked
0
LimLodA
ASG
Limit load current (LTC block load current)
0
VLCEnable
SPG
enable or disable VLC
0
VRedVal
ASG
Reduction of band center (percent) when voltage reduction step
is active
0
TapChgTyp
ENG
Tap changer type.
E
RegTyp
ENG
Regulator type
E
Syst
ENG
System wiring configuration
E
DeltaPwr
SPG
Delta power configuration
E
UtilPol
ENG
Utility winding polarity
E
VPrimMax
ENG
Maximum primary voltage
E
U2PTPri
ING
Utility winding primary side
E
U2PTSec
ING
Utility winding secondary side
E
P2PTPri
ING
Potential transformer turns primary side
E
P2PTSec
ING
Potential transformer turns secondary side
E
CTPri
ING
Current transformer turns primary side
E
CTSec
ING
Current transformer turns secondary side
E
IFullLoad
ING
Regulating device full load rating
E
NeutOvRun
ASG
Neutral over run
E
PwrFlow
ENG
Power flow modes
E
BasVlt
ENG
Controller nominal voltage level
E
MeterVolt
SPG
Meter Display Volts
Ithres
ING
Tap change minimum current (0 to 10% - default 0%)
E
Ishift
ING
Current shift for reverse power flow (0° to 349° - default 0°)
E
ILodMax
ING
Max. load current (for overcurrent) (0% to 350% - default 350%)
E
PTthres
ING
Tap change low voltage limit (0 to 134 - default 90)
E
DmdType
ENG
Method for determining command
E
DmdTime
ING
Demand period length (minutes) (1 to 999 - default 30)
E
DmdSubPer
ING
Number of demand subperiods (for sliding window mode only)
E
AutoVariAmp
SPG
Automatic Variamp protection
E
SoftVariAmp
SPG
Software Variamp setting
E
Rlimit
ENG
Raise limit (Alter & Soft Variamp)
E
Llimit
ENG
Lower limit (Alter & Soft Variamp)
E
SlaveMaster
ENG
Put two tap changers in locked step
E
TapAlertEna
SPG
Enable or disable tap alert
E
TapResync
SPG
Synchronizes tap position at neutral
E
RLOnTime
ASG
maximum time to keep the tap changer motor running before
pausing for RLOffTime (in seconds)
E