22
0
Fwd Voltage Level
1
Fwd Bandwidth
2
Fwd Time Delay
3
Clear Contact Statuses and Op Counters
4
Read Overall Status of Contacts
6.2.9
2.x3
Binary Inputs
Point #
Scale Factor
Description
0
SF = 1
Tap Pos Known
1
SF = 1
Power Flow Direction
2
SF = 1
Auto Inhibit Status
3
SF = 1
Raise (J) Motor Signal
4
SF = 1
Lower (K) Motor Signal
5
SF = 1
Remote Control occurring
6
SF = 1
U2/P2 Switch Position
7
SF = 1
Neutral (U12) Signal
8
SF = 1
Operations Count (U10) Signal
9
SF = 1
Auto Inhibit Terminal Block Input
10
SF = 1
VRC1 contacts
11
SF = 1
VRC2 contacts
12
SF = 1
Remote Switch position
13
SF = 1
Manual Switch position
14
SF = 1
Auto Inhibit Out Status
Binary Outputs
Point #
Scale Factor
Description
0
SF = 1
Tap Raise
1
SF = 1
Tap Lower
2
SF = 1
Auto Inhibit (Latch On/Off)
Analog Inputs
Point #
Scale Factor
Description
0
Op Count Last Year
1
N/A
2
SF = 1
R/A/M switch position
3
Power Flow Direction Indicator
4
SF = 1
VRC contacts status
5
SF = 1
Band, VRC, VLC status
6
SF = 1
Tap Position
7
SF = 1
Load Current
8
SF= 10
Load Voltage
9
SF= 0.1
Load Voltage (primary)
10
SF= 10
Source Voltage
11
SF= 0.1
Source Voltage (primary)
12
SF = 1
KVA
13
SF = 1
KVAR
14
SF = 1
KW
15
SF= 100
Power Factor
16
SF = 10
P2 Ratio
17
variable
Ld Current Dmd (Fwd Present)
18
SF = 1
kVA Dmd (Fwd Present)
19
SF = 1
kVAR Dmd (Fwd Present)
20
SF = 1
kW Dmd (Fwd Present)
21
SF= 10
Load Volts Dmd (Fwd Present)
22
SF= 10
CompVolts Dmd (Fwd Present)
23
variable
Load I Dmd (Rev Present) (Amps)
24
SF = 1
kVA Load Dmd (Rev Present)
25
SF = 1
kVAR Load Dmd (Rev Present)