33
RLOffTime
ASG
pause between tap changes for this amount of time (in seconds)
E
RLOnTimeFix
SPG
when in auto mode motor stays on for exactly RLOnTime
seconds
E
TapChgTms
ASG
timeout for tap changer motor running when no operation count
occurs.
E
TapIn
ENG
defines the operations count signal input line (1 = U10, 2 = HS)
E
TapInType
ENG
defines the operations counter type (1 = toggle, 2 = pulse)
E
TapInPlsTm
ASG
defines the minimum amount of time that an operations count
signal must be present in order for the operations counter to
increment (applies to pulse type operations counters only)
E
NeutIn
ENG
defines the neutral signal input line (1 = U12, 2 = U112, 3 =
NONE)
E
NeutCnt
ING
number of neutral positions
E
BndCtrRev
ASG
Voltage setpoint level for reverse power flow
E
BndWidRev
ASG
Bandwidth voltage reverse power flow
E
CtIDITmmsRev
ING
Control intentional time delay (in s) for reverse power flow
E
LDCRRev
ASG
Line drop voltage due to line resistance component (reverse
flow)
E
LDCXRev
ASG
Line drop voltage due to line reactive component (reverse flow)
E
VredMod
ENG
Voltage reduction control mode
E
AltDl
ING
Alternate time delay for voltage reductions (in seconds)
E
VRC1In
ENG
VRC1 contact configuration
E
VRC2In
ENG
VRC2 contact configuration
E
VRCEmuMod
ENG
MJ-X or MJ-3A emulation mode
E
VRCStg1
ASG
Voltage reduction first stage (in %)
E
VRCStg2
ASG
Voltage reduction second stage (in %)
E
VRCStg3
ASG
Voltage reduction third stage (in %)
E
AutoVRC1
ASG
VRC setting #1 for Auto VRC (in %)
E
AutoVRC2
ASG
VRC setting #2 for Auto VRC (in %)
E
AutoVRCAmp1
ASG
Load current #1 for Auto VRC (in %)
E
AutoVRCAmp2
ASG
Load current #2 for Auto VRC (in %)
E
Opcount
UING
Operation counter
Condition C1: depending on the tap-change method, at least one of the two controls, TapChg or TapPos shall be
used for manual operation. BndCtrChg may be optionally used to change the value of BndCtr by commands.