Maintenance
12
Building Technologies
FL-III Maintenance and Repair
CPS Fire Safety
08.2012
Panel LED
Designation
Colour Function
Optical ports
LASER ON
Green
Laser operation is enabled.
Power supply
POWER ON
Green
Power supply is operating.
Tab. 2
LED’s on the rear side of the FibroLaser III controller
Incident Mode
Duration
(Sequence)
Power on
Long single beep
Few seconds.
Ping (Test of IP connection)
Fast periodic
beeping
3 s
(0.07 s on / 0.03 s off)
Fault (not acknowledged)
Slow periodic
beeping
Permanent
(0.7 s on / 0.3 s off)
Alarm (not acknowledged)
Continuous beeping
Permanent
Tab. 3
Acoustic signals of the FibroLaser III controller
Actuation Function
Action
Right, short
(< 3 s)
Acknowledgement All alarms and pre-alarms are acknowledged.
The buzzer is deactivated.
Right, long
(> 3 s)
Reset
All alarms, pre-alarms, faults and manual reset
out-puts are reset if they are no longer active.
The corre-sponding alarm, pre-alarm and fibre
or system fault LED’s are deactivated. Self-
reset outputs are also reset if this function is
activated (see Operation Manual).
Left
(engaged)
Test mode
The controller is operated in the test mode.
Tab. 4
Functions of the key switch of the FibroLaser III controller