Engineering via SICAM WEB
416
Unrestricted
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
Example: Setpoint command, normalized
•
In the directory tree, mark the corresponding AO module
•
Click on the side bar left beside the status area, if you want to extend it
•
Mark the row with the desired datapoint
Control area:
•
Select a “New value”
The data format corresponds to the setting of the data point on the I/O Module (signal list).
•
Select the “Select before execute“ option
With selection
Yes
and button you activate the select command. You activate the ex-
ecute command, when you click on the button once more within the adjusted time
(
select_execute_t
).
With selection
No
and button you activate the execute command directly.
The new process value is transferred to the target device and displayed in the column V
ALUE
.
You find further details in the manual
SICAM RTUs Common Functions Peripheral Elements
According to IEC 60870-5-101/104,
chapter
"Setpoint Values by means of Currents and Volt-
ages", section "Select and Execute Command"
.
Содержание CP-8000
Страница 10: ...Open Source Software 10 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 74: ...Function Packages 74 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 468: ...Engineering via SICAM WEB 468 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 524: ...Service 524 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 556: ...Error Handling 556 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 603: ...Use Cases SICAM A8000 CP 8000 CP 8021 CP 8022 Manual Unrestricted 603 DC8 037 2 02 Edition 10 2017 ...
Страница 604: ......