Engineering via SICAM WEB
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
Unrestricted
383
DC8-037-2.02, Edition 10.2017
Processing type
Parameter
Meaning
DO_SC_1,5POL – single
command output 1,5-pole
Retry_suppression_T
Command retry suppression time in seconds.
Within this time a command with same ad-
dress is discarded without error information (s)
0.1 to 6553.5
Output_t
Command output time in seconds (S).
Attention: The time comes into effect only, if in
the message is not defined any time.
0.01 to 327.67
select_execute_t
Max. time between select and execute (in
seconds). After this time a recent select com-
mand is necessary.
0 = no select command is expected (direct
command transmission)
0.1 to 102.3
Sync_t
Within this time (in sec) the interlock enabling
must occur on the command.
0 = no syncronisation over interlocking
0.1 to 6553.5
RS_Mon_t
Return state information monitoring time in
seconds (S).
0 = no return state information monitoring
0.01 to 655.35
Command_prolong_t
Command prolongation time in seconds (S)
0.01 to 327.67
RS_outp_same_state_1
Selection of command output and command
confirmation, if return state is already end
position before output.
Attention: only active if RS_mon_t is
≠
0.
Sync_Input_t
Within this time (in sec) the enabling over the
syncronisation input must occur on the com-
mand.
0 = no syncronisation over syncronisation
input.
Attention: Function only active if sync_t = 0
0.1 to 6553.5
1_out_of_n_t
Within this time (in sec) the 1 out of n enabling
must occur on the command.
0 = no 1 out of n enabling necessary.
Attention: Function only active if sync_t = 0.
0.1 to 25.5
RS_Mon_Source
Source of state information for state infor-
mation monitoring
•
Peripherals
•
Open-/closed loop control function
•
Both (logical OR)
Sw_Seq_command_seq
Switching sequence: output additional com-
mand before or after the command
Sw_Seq_addtl_com
Switching sequence: Select the additional
command
SID-BSE
Source identification basic system element
SID-ST
Source identification station number if mul-
tipoint traffic mode 0…99 if R-SID 0…254; if
automatic, the SID will be learned
Содержание CP-8000
Страница 10: ...Open Source Software 10 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 74: ...Function Packages 74 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 468: ...Engineering via SICAM WEB 468 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 524: ...Service 524 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 556: ...Error Handling 556 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 603: ...Use Cases SICAM A8000 CP 8000 CP 8021 CP 8022 Manual Unrestricted 603 DC8 037 2 02 Edition 10 2017 ...
Страница 604: ......