9.1.13.2.1 Supported Type Identifications and Possible Values
Type Identification
Possible value
Single-point information
(TI 30)
Off (0)
On (1)
Double-point information
(TI 31)
Intermediate (00),
Off (01)
On (10)
Error (11)
Single command (TI 45)
Off (0)
On (1)
Double command (TI 46)
Terminated (00)
Off (01)
On (10)
Error (11)
Tap position command (TI 47)
Terminated (00)
Lower (01)
Higher (10)
Error (11)
Counter value (TI 37)
Measured value normalized
(TI 34)
-1…+1
-15
Measured value scaled (TI 35)
-32768…+32767 (15 Bit + sign)
Measured value short floating
point (TI 36)
-1.000•10
15
…+1.000•10
15
Setpoint normalized (TI 48)
-1…+1
-15
Setpoint scaled (TI 49)
-32768…+32767 (15 Bit + sign)
Setpoint short floating point
(TI 50)
-1.000•10
15
…+1.000•10
15
Value from device without conversion
The values are converted depending on the type identification (TI). Analog values are dis-
played as conditioned values.
The data format of the displayed inputs corresponds to the setting of the respective data point
on the I/O Module (signal list).
Содержание CP-8000
Страница 10: ...Open Source Software 10 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 74: ...Function Packages 74 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 468: ...Engineering via SICAM WEB 468 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 524: ...Service 524 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 556: ...Error Handling 556 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 603: ...Use Cases SICAM A8000 CP 8000 CP 8021 CP 8022 Manual Unrestricted 603 DC8 037 2 02 Edition 10 2017 ...
Страница 604: ......