Engineering via SICAM WEB
360
Unrestricted
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
9.1.11.2.2 Parameters with Assignment on the Master Module
This data can be changed – for each category – in the table for the signal generation:
Category
Parameter
Meaning
Communication control
message
Control_function_(COM)
•
Revision function
•
Test function
•
Block function
PRE
Protocol element
Station_(COM)
Station number (selective 0…99 or all)
CASDU1_(COM)
Address of the datapoint. The complete
address consists of CASDU1, CASDU2,
IOA1, IOA2 and IOA3. CASDU1 and
CASDU2 = 255 means no spontaneous
transmission.
CASDU2_(COM)
Address of the datapoint. The complete
address consists of CASDU1, CASDU2,
IOA1, IOA2 and IOA3. CASDU1 and
CASDU2 = 255 means no spontaneous
transmission.
Function_group_(COM)
Function group number (0…255)
SID-BSE
Source identification basic system element
SID-ST
Source identification station number if mul-
tipoint traffic mode 0…99 if R-SID 0…254; if
automatic, the SID will be learned
SID-SSE
Source identification supplementary system
element
Decentral archiving
Function_(DEAR)
•
Archive data
•
Address main directory
•
Address subdirectory
•
Address file
SID-BSE
Source identification basic system element
SID-ST
Source identification station number if mul-
tipoint traffic mode 0…99 if R-SID 0…254; if
automatic, the SID will be learned
SID-SSE
Source identification supplementary system
element
Error message detailed
diagnostics table
SSE
Supplementary system element
Diagnostic_class
In case of "all bits, all records, all classes" the
parameter "diagnostic record" and "diagnostic
bit" are not significant
Diagnostic_record
Diagnostic record 0…254 = record number
whitin the selected diagnostic class
255 = sum of all bits of all records (the pa-
rameter "diagnostic bit" is not significant)
Diagnostic_bit
Bit number (0…15; all bits)
Error message sum diag-
nostics table
Error_location/BSE
Error location/basic system element
Error_location/SSE
Error location /supplementary system ele-
ment
Error type
Error class in the diagnosis
Содержание CP-8000
Страница 10: ...Open Source Software 10 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 74: ...Function Packages 74 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 468: ...Engineering via SICAM WEB 468 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 524: ...Service 524 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 556: ...Error Handling 556 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 603: ...Use Cases SICAM A8000 CP 8000 CP 8021 CP 8022 Manual Unrestricted 603 DC8 037 2 02 Edition 10 2017 ...
Страница 604: ......