CERBERUS PYROTRONICS
TM
System PXL
CONNECTION
DIAGRAM
Listed as a coded/noncoded local fire alarm control unit for automatic or
manual service, for sprinkler supervisory service, and for waterflow
service in accordance with NFPA 72 Local. Also approved as an NFPA 72
Central Station Protective Premises Control Unit and as an NFPA 72
Remote Station Control Unit.
PXL FUSE REPLACEMENT
FUSE
DESCRIPTION
VALUE
F1
F2
F3
F4
XFORM SEC
BATTERY
AUX POWER
+24 VDC
20.0A, 250V, Normal Blow
20.0A, 250V, Normal Blow
1.50A, 250V, Normal Blow
1.00A, 250V, Normal Blow
*
When a zone is in alarm, each IDC can operate the following:
one ionization or photoelectric type smoke detector, or one PBA-1191 linear
beam smoke detector
one relay base, or audible base, or remote alarm lamp
**
When determining quantity of shorting devices, use sound engineering judgement.
***
Do not mix the PBA-1191 beam detector and any other device on the same zone.
The PBA-1191 can only be connected as Class B.
NOTE:
In all cases the Siemens Building Technologies, Inc. model number is the
compatibility identifier.
ELECTRICAL RATINGS
Supervisory
Alarm
PCM-1 (IDC)
20.0-26.4 VDC
8.5mA max
20.0-26.4 VDC
180mA max
PZE-4B (IDC)
Class B
20.0-26.4 VDC
8.5mA max
20.0-26.4 VDC
180mA max
PNC-2Z (NAC)
24 VDC Nominal
2.4mA max
24 VDC Nominal
2A max
PPS-10M (NAC)
24 VDC Nominal
2.4mA max
24 VDC Nominal
2A max
PPS-10M (Relays)
30 VDC / 120 VAC
5A max resistive
30 VDC / 120 VAC
5A max resistive
PPS-10M (Serial Bus)
400mA, 24V
400mA, 24V
PRM-4
30 VDC / 120 VAC
5A max resistive
30 VDC / 120 VAC
5A max resistive
LED-3/-4
24 VDC
10mA max
24 VDC
10mA + 2mA
per LED max
RSA-16
24 VDC
20mA max
24 VDC
20mA + 13mA
per LED max
NOTES:
1. All wiring must comply with local and national codes.
2. Make no wiring connections while the System is powered.
3. Relay Contacts are shown de-energized. Suitable for resistive load only.
4. Refer to the
PXL Operation, Installation, and Maintenance Manual,
P/N 315-094131, for
further details.
5. No T-Tapping allowed.
6. Connect standby batteries only to terminals BAT+ and BAT-. The batteries may be installed in
either the bottom of the cabinet or in a UL listed battery enclosure.
7. In all cases the Siemens Building Technologies, Inc. model number is the compatibility identi-
fier, including the control panel, module(s), and all compatible initiating devices.
8. All power limited wiring requires separation from non-power limited wiring. Refer to the
PSE-1
Installation and Power Limited Wiring Instructions,
P/N 315-094154.
9. Combination of NAC power and AUX power can be no greater than 10A.
10. Use up to 65AH lead-acid battery only. Battery charging current is 2A max.
COMPATIBLE DETECTORS*
Detector
Quantity
per
Loop
Base
Installation
Instructions
Part No.
DI-3/3H
30
DB-3S
315-081943-16
DI-A3/A3H
30
DB-3S
315-081943-16
DI-B3/B3H
30
AD-3I
315-093234-5
DT-11
30
DB-11
DB-3S with DB-ADPT
315-095429-2
315-095429-2
PBA-1191***
1
PBB-1191
315-095424-3
PE-3
30
DB-3S
AD-3ILP
315-081943-16
315-093234-5
PE-11/11T
30
DB-11
DB-3S with DB-ADPT
AD-11P/11PR
315-094198-7
315-094198-7
315-095659-6
11. Canadian systems require automatic battery disconnect. Refer to Appendix C of the
PXL Op-
eration, Installation, and Maintenance Manual,
P/N 315-094131, for wiring information.
12. Up to 8 LED-3/-4 modules may be connected to the serial bus (TB5). For further information,
refer to the
LED-3/-4 Installation Instructions,
P/N 315-093066. Up to 4 (6) RSA-16/RSA-DRIVs
may be connected to the serial bus (TB5). Refer to the
RSA-16
or
RSA-DRIV Installation In-
structions,
P/N 315-096035 or P/N 315-095898, as applicable. When 2 PPS-10M modules are
used, connect all RSA/LED modules to the first PPS-10M.
13. When initiating circuits are configured as supervisory type zones, only shorting devices may be
used.
14. When 2 PPS-10M power supplies are used, cut jumper JP3 on the second PPS-10M.
15. When 2 PPS-10M power supplies are used, the serial bus, TB5, on the second PPS-10M is
disabled.
16. Generic and Supervisory zones must use shorting devices only.
17. For a list of
Compatible Notification Appliances,
refer to P/N 315-096363.
18. When connecting between two PPS-10Ms, cut and remove the red wires from the 15" cable in the
PCK-1 kit (P/N 500-695066).
P/N 575-295093-5