PXL Conventional Fire Alarm Control Panel
Installation
12
STEP 4Install the Optional PRM-4
CAUTION
The PPS-10M Power Supply module must be installed before
mounting and wiring the PRM-4
Relay module.
Setting the Address
Before mounting the PRM-4 to the PMK-1 bracket, set the address on
Switch S1 according to Table 2. (Refer to Figure 7 for the location of S1
and to the Note on page 9 for the operation of the switches.)
TABLE 2
SETTING THE ADDRESS ON THE PRM-4
Module
Number
Relay
Range
Switch Setting
1 2 3 4 5
1
1-4
X
O
O
O
O
2
5-8
O
X
O
O
O
3
9-12
X
X
O
O
O
4
13-16
O
O
X
O
O
5
17-20
X
O
X
O
O
6
21-24
O
X
X
O
O
7
25-28
X
X
X
O
O
8
29-32
O
O
O
X
O
X = SWITCH CLOSED OR ON, O = SWITCH OPEN OR OFF
Figure 7
PRM-4 Module Board
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com