Chapter 5) 7SR23 DAD Installation Guide
©2013 Siemens Protection Devices Limited
Chapter 5 Page 18 of 24
6.4 Optional Additional RS485 Connections
The additional (optional) RS485 communication port is located at the rear of the relay and can be connected
using a suitable RS485 120 ohm screened twisted pair cable.
The RS485 electrical connection can be used in a single or multi-drop configuration. When used with Reydisp the
RS485 master must support and use the Auto Device Enable (ADE) feature.
The last device in the connection must be terminated correctly in accordance with the master device driving the
connection. The relays are fitted with an internal terminating resistor which can be connected between the A and
B by fitting an external wire loop between terminals 18 and 20 on the power supply module.
6.5 Optional RS232 Connections
The additional (optional) RS232 (9 pin plug) (DTE) communication port is located at the rear of the relay and can
be connected using a suitable RS232 cable.
Where there is a requirement for multi-drop RS232 connection, a suitable device to facilitate this should be
obtained.
Pin
Relay Function
1
Not
Connected
2
Receive Data (RXD)
3
Transmit Data (TXD)
4
Output 5V 50mA
5
Signal Ground (GND)
6
Output 5V 50mA
7
Linked to 8 (volts free)
8
Linked to 7 (volts free)
9
Output 5V 50mA
Figure 6.5-1 RS232 Data Comms Pin Connections
Содержание 7SR23 DAD
Страница 1: ...Answers for energy 7SR23 DAD High Impedance Protection Relay Reyrolle Protection Devices ...
Страница 2: ......
Страница 4: ...7SR23 DAD Contents 2013 Siemens Protection Devices Limited ...
Страница 40: ...Chapter 1 7SR23 DAD Description Of Operation 2013 Siemens Protection Devices Limited Chapter 1 Page 36 of 36 ...
Страница 60: ...Chapter 3 7SR23 DAD Performance Specification 2013 Siemens Protection Devices Limited ...
Страница 78: ...Chapter 3 7SR23 DAD Performance Specification 2013 Siemens Protection Devices Limited Chapter 3 Page 20 of 20 ...
Страница 80: ...Chapter 4 7SR23 DAD Data Communications 2013 Siemens Protection Devices Limited Chapter 4 Page 2 of 54 ...
Страница 134: ...Chapter 5 7SR23 DAD Installation Guide 2013 Siemens Protection Devices Limited Chapter 5 Page 2 of 24 ...
Страница 156: ...Chapter 5 7SR23 DAD Installation Guide 2013 Siemens Protection Devices Limited Chapter 5 Page 24 of 24 ...
Страница 158: ...Chapter 6 7SR23 DAD Commissioning Maintenance Guide 2013 Siemens Protection Devices Limited Chapter 6 Page 2 of 26 ...
Страница 182: ...Chapter 6 7SR23 DAD Commissioning Maintenance Guide 2013 Siemens Protection Devices Limited Chapter 6 Page 26 of 26 ...
Страница 184: ...Chapter 7 7SR23 DAD Applications Guide 2013 Siemens Protection Devices Limited Chapter 7 Page 2 of 42 ...
Страница 224: ...Chapter 7 7SR23 DAD Applications Guide 2013 Siemens Protection Devices Limited Chapter 7 Page 42 of 42 ...
Страница 225: ......