Trip Circuit Supervision (74TCS)
Binary Inputs may be used to monitor the integrity of the CB trip circuit wiring. Current flows through the B.I.
confirming the integrity of the auxiliary supply, CB trip coil, auxiliary switch, C.B. secondary isolating contacts and
associated wiring connected to that BI. If the current flow ceases, the B.I. drops off and if it is user programmed to
operate one of the output relays, this can be used to provide an alarm. In addition, an LED on the relay fascia can
be programmed to operate. A user text label can be used to define the operated LED e.g. “Trip CCT Fail”.
The relevant Binary Input is mapped to 74TCS-n in the INPUT CONFIG>INPUT MATRIX menu. To avoid giving
spurious alarm messages while the circuit breaker is operating the input is given a 0.4s Drop-off Delay in the
INPUT CONFIG>BINARY INPUT CONFIG menu.
To provide an alarm output a normally open binary output is mapped to 74TCS-n.
5.2.1
Trip Circuit Supervision Connections
The following circuits are derived from UK ENA S15 standard schemes H5, H6 and H7.
For compliance with this standard:
Where more than one device is used to trip the CB then connections should be looped between the
tripping contacts. To ensure that all wiring is monitored the binary input must be at the end of the looped
wiring.
Resistors must be continuously rated and where possible should be of wire-wound construction.
Scheme 1 (Basic)
Figure 5-1
Trip Circuit Supervision Scheme 1 (H5)
Scheme 1 provides full Trip and Close supervision with the circuit breaker Open or Closed.
Where a ‘Hand Reset’ Trip contact is used measures must be taken to inhibit alarm indications after a CB trip.
Содержание 7SR23 DAD
Страница 1: ...Answers for energy 7SR23 DAD High Impedance Protection Relay Reyrolle Protection Devices ...
Страница 2: ......
Страница 4: ...7SR23 DAD Contents 2013 Siemens Protection Devices Limited ...
Страница 40: ...Chapter 1 7SR23 DAD Description Of Operation 2013 Siemens Protection Devices Limited Chapter 1 Page 36 of 36 ...
Страница 60: ...Chapter 3 7SR23 DAD Performance Specification 2013 Siemens Protection Devices Limited ...
Страница 78: ...Chapter 3 7SR23 DAD Performance Specification 2013 Siemens Protection Devices Limited Chapter 3 Page 20 of 20 ...
Страница 80: ...Chapter 4 7SR23 DAD Data Communications 2013 Siemens Protection Devices Limited Chapter 4 Page 2 of 54 ...
Страница 134: ...Chapter 5 7SR23 DAD Installation Guide 2013 Siemens Protection Devices Limited Chapter 5 Page 2 of 24 ...
Страница 156: ...Chapter 5 7SR23 DAD Installation Guide 2013 Siemens Protection Devices Limited Chapter 5 Page 24 of 24 ...
Страница 158: ...Chapter 6 7SR23 DAD Commissioning Maintenance Guide 2013 Siemens Protection Devices Limited Chapter 6 Page 2 of 26 ...
Страница 182: ...Chapter 6 7SR23 DAD Commissioning Maintenance Guide 2013 Siemens Protection Devices Limited Chapter 6 Page 26 of 26 ...
Страница 184: ...Chapter 7 7SR23 DAD Applications Guide 2013 Siemens Protection Devices Limited Chapter 7 Page 2 of 42 ...
Страница 224: ...Chapter 7 7SR23 DAD Applications Guide 2013 Siemens Protection Devices Limited Chapter 7 Page 42 of 42 ...
Страница 225: ......