Chapter 7) 7SR23 DAD Applications Guide
©2013 Siemens Protection Devices Limited
Chapter 7 Page 9 of 42
2.1.2
Establishing the Required Stabilising Resistor Value
The relay burden need not be considered as it is effectively negligible relative to the burden of the stabilising
resistor. The setting (operate) voltage (Vs) across the Relay and Stabilising Resistor at the Relay operating
current (Is):
S
S
STAB
I
V
R
(4)
Stabilising Resistor power rating must:
Be sufficient for continuous operation at the circuit operate voltage (Vs):
stab
2
s
CONT
R
x
)
(I
P
Short time rated to withstand I
Fint
for the maximum fault clearance time. For a failed circuit breaker
condition the back up protection clearance time is considered – typically a one second rating is sufficient.
R
V
P
stab
2
Fint
1SEC
Where:
1.3
x
)
I
x
R
x
(V
V
4
Fint
stab
3
K
Fint
Where I
Fint
is not known, the breaking capacity current of the Circuit Breaker can be used.
2.1.3
Limiting Circuit Over-Voltages (Metrosils)
Non-linear resistors are connected in parallel with the relay circuit to limit the peak voltage developed across the
high impedance components during internal faults to a ‘safe’ level below 3kV peak. Where a Metrosil is not
connected in circuit the peak voltage can be calculated from:
)
V
-
R
I
(
x V
2
x
2
V
K
stab
Fint
K x
Pk
Notwithstanding the above calculation SPDL recommend that a Metrosil is always fitted in the high impedance
relay circuit
The use of non-linear resistors manufactured by Metrosil is recommended. The operate characteristic is defined
by:-
Voltage characteristic:
I
C
V
.
For dc or instantaneous values.
1
2
52
.
0
C
Vrms
Irms
For applied sinusoidal voltages
)
(
09
.
1
Irms
C
Vpeak
For applied sinusoidal currents
Where: C and are Metrosil constants
When supplied as discrete components 7XG14 Metrosils can be specified as single or three phase, with a
diameter of 75mm or 150mm and have constant ‘C’ values of 450, 900 or 1000.
Metrosils of diameter 75mm have a thermal rating of 8kJ. Where a higher thermal rating is required Metrosils of
150mm diameter should be used.
The optional component box includes both three phase resistors and three phase Metrosils. Metrosils in the
component box have a ‘C’ value of 1000.
Содержание 7SR23 DAD
Страница 1: ...Answers for energy 7SR23 DAD High Impedance Protection Relay Reyrolle Protection Devices ...
Страница 2: ......
Страница 4: ...7SR23 DAD Contents 2013 Siemens Protection Devices Limited ...
Страница 40: ...Chapter 1 7SR23 DAD Description Of Operation 2013 Siemens Protection Devices Limited Chapter 1 Page 36 of 36 ...
Страница 60: ...Chapter 3 7SR23 DAD Performance Specification 2013 Siemens Protection Devices Limited ...
Страница 78: ...Chapter 3 7SR23 DAD Performance Specification 2013 Siemens Protection Devices Limited Chapter 3 Page 20 of 20 ...
Страница 80: ...Chapter 4 7SR23 DAD Data Communications 2013 Siemens Protection Devices Limited Chapter 4 Page 2 of 54 ...
Страница 134: ...Chapter 5 7SR23 DAD Installation Guide 2013 Siemens Protection Devices Limited Chapter 5 Page 2 of 24 ...
Страница 156: ...Chapter 5 7SR23 DAD Installation Guide 2013 Siemens Protection Devices Limited Chapter 5 Page 24 of 24 ...
Страница 158: ...Chapter 6 7SR23 DAD Commissioning Maintenance Guide 2013 Siemens Protection Devices Limited Chapter 6 Page 2 of 26 ...
Страница 182: ...Chapter 6 7SR23 DAD Commissioning Maintenance Guide 2013 Siemens Protection Devices Limited Chapter 6 Page 26 of 26 ...
Страница 184: ...Chapter 7 7SR23 DAD Applications Guide 2013 Siemens Protection Devices Limited Chapter 7 Page 2 of 42 ...
Страница 224: ...Chapter 7 7SR23 DAD Applications Guide 2013 Siemens Protection Devices Limited Chapter 7 Page 42 of 42 ...
Страница 225: ......