
Page 38
SITRANS LG200 – INSTRUCTION MANUAL
7ML19985KA02
Wiring
2. Intrinsically Safe Wiring
An intrinsically safe (IS) installation potentially has flammable media present. An
approved IS barrier must be installed in the non-hazardous (safe) area. Observe electrical
data below:
1.
Install a suitable IS barrier in the non-hazardous (safe) area. Complete the wiring
from the barrier to the SITRANS LG200 transmitter. (refer to local plant or facility
procedures)
2.
Unscrew and remove the enclosure lid.
3.
Install a cable gland in the conduit entry. Use PTFE tape/sealant to ensure a liquid-
tight connection.
4.
Install a conduit fitting and feed the supply wires into the SITRANS LG200 through
the conduit entry.
5.
Connect shield to an earth ground at power supply.
6.
Connect an earth ground wire to the nearest green ground screw.
7.
Connect the positive supply wire to the (+) terminal and the negative supply wire to
the (-) terminal.
8.
Replace the enclosure lid.
Note:
• Electrical data for SITRANS LG200 Level Transmitter Model 7ML1300-1Axx1-xCA0:
Output/supply circuit (ter and -):
in type of protection intrinsic safety EEx ia IIC, only for connection to a certified
intrinsically safe circuit, with the following maximum values:
Ui = 28,4 V; Ii = 94 mA; Pi = 0,67 W; Ci = 2,2 nF; Li = 3
μ
H. or
• Electrical data in type of protection intrinsic safety EEx ia IIC, only for connection to a
certified intrinsically safe circuit, with the following maximum values:
Ui = 28,4 V; Ii = 94 mA; Pi = 0,67 W; Ci = 3 nF; Li = 3
μ
H.
WARNING: If flammable media is contained in the vessel, the
transmitter must be installed per Class I, Div. 1 ATEX II 1/2 GD EEx d
[ia] (Explosion Proof) standards of area classification.
Содержание 7ML1301-1
Страница 1: ...Instruction Manual February 2009 LG200 sitrans ...
Страница 10: ...Page 6 SITRANS LG200 INSTRUCTION MANUAL 7ML19985KA02 SITRANS LG200 Notes ...
Страница 59: ...7ML19985KA02 SITRANS LG200 INSTRUCTION MANUAL Page 55 SIMATIC PDM ...
Страница 60: ...Page 56 SITRANS LG200 INSTRUCTION MANUAL 7ML19985KA02 SIMATIC PDM Notes ...
Страница 96: ...Page 92 SITRANS LG200 INSTRUCTION MANUAL 7ML19985KA02 Hazardous Installation ...