Enter code (menu 6.1)
Programming of the device by unauthorized persons can be prevented using a personal code
(range 1 to 9999; max. four digits). By entering the correct code in this menu, the programming
is enabled and the device settings can be changed (the general write protection must be
disabled on the PROFIBUS (WRITE_LOCKING parameter).
If you have forgotten the code, enter 3333 in menu 6.1 and the personal code will be displayed
for 5 seconds.
Customer Code (menu 6.2)
The four-digit personal code number can be created in this menu. The local write protection is
activated for values > 0, that is menus can still be accessed but parameters cannot be changed.
The write protection is automatically enabled the next time the system is switched to the initial
operating view.
Note
Attention
Programming is permanently enabled as long as the code is 0 and the general write protection
is not enabled on the PROFIBUS (WRITE_LOCKING parameter)..
Service code (menu 6.3)
The calibration data and factory settings of the device are protected by a service code. The
relevant menus are available only after entering this service code. For normal operation it is not
required to enter the service code.
Reset (menu 6.4)
A reset of the unit can be made without change of parameters (warm restart). Totalizers are not
reset.
Control values (menu 6.5)
In this menu, device-internal data used mainly for diagnosis for the used paths can be read.
The values displayed in the individual menu depend on the respective application (medium).
The following data are available:
• Gain
• Amplitudes
• Trigger level
• Error count %
• Time of flight - up (TOF up)
Functions
7.6 Service (menu 6)
SITRANS FUS060 with PROFIBUS PA
Operating Instructions, 09/2021, A5E02225054-AD
65