EN IEC 60079-0:2018; EN 60079-1:2014, EN IEC 60079-7:2015+A1:2018, EN 60079-11:2012,
EN 60079-18:2015/A1:2017
WARNING
Field wiring installation
Make sure the hazardous area approval is suitable for the environment in which the device will
be installed.
Intrinsically safe data
Power supply
19.2 V to 30 V DC, approximately 10 W or 20.4 to 26.4 V AC, approximately 10 VA
Fuse: 4 A / breaking capacity 1500 A
Intrinsically safe data
Only for connection to a certified intrinsically safe circuit (e.g. FISCO-power supply unit) with
maximum values of:
PROFIBUS PA output
(Terminals 7+ and 8-)
FISCO power supply unit ia/ib
group IIC/IIB
Linear barrier ia/ib IIC/IIB
(active output)
U
o
17.5 V
24 V
I
o
380 mA
250 mA
P
o
5.32 W
1.2 W
Digital output 1 (pulse/frequency/limit)
(Terminals 5+ and 6-)
Ex ia IIC/IIB or Ex ib IIC/IIB
(passive output)
U
i
30 V
I
i
100 mA
C
i
24 nF
L
i
108 μH
P
i
750 mW
Digital output 2 (relay)
(Terminals 3+ and 4-)
Ex ia IIC/IIB or Ex ib IIC/IIB
(passive output)
U
i
30 V
I
i
100 mA (DC), 50 mA (AC)
C
i
24 nF
L
i
73 μH
Safety notes
2.3 Installation in hazardous area
SITRANS FUS060 with PROFIBUS PA
Operating Instructions, 09/2021, A5E02225054-AD
13