Addressing the communication parameters
Table A- 9
Addressing the communication parameters
Offset Number of
registers
Name
Format
Unit
Value range from
... to
Access
63019 2
ModbusRTU address
unsigned long
1 … 247
RW
63021 2
ModbusRTU baud rate
unsigned long
0 … 5
•
0 = 4800 baud
•
1 = 9600 baud
•
2 = 19200 baud
•
3 = 38400 baud
•
4 = 57600 baud
•
5 =
115200 baud
RW
63023 2
ModbusRTU data bits/parity/stop
bits
unsigned long
0 … 3
•
0 = 8N2
•
1 = 8E1
•
2 = 8O1
•
3 = 8N1
RW
63025 2
ModbusRTU response time
unsigned long
ms
0 … 255
RW
Addressing the settings for the I&M data
Table A- 10 Addressing the settings for the I&M data
Offset Number of
registers
Name
Format
Applicable Modbus
function codes
Access
64001 27
I&M 0 data
stIM0
•
0x03
•
0x04
R
64028 89
I&M 1 data … I&M 4 data
stIM14
•
0x03
•
0x04
•
0x10
RW
Содержание 7KM1020-0BA01-1DA0
Страница 1: ......
Страница 2: ......
Страница 8: ...Table of contents PAC1020 6 Equipment Manual 05 2020 L1V30610008B 01 ...
Страница 22: ......
Страница 44: ...Commissioning 5 6 Checking the displayed measured values PAC1020 42 Equipment Manual 05 2020 L1V30610008B 01 ...
Страница 50: ...Operation 6 1 Device interface PAC1020 48 Equipment Manual 05 2020 L1V30610008B 01 ...
Страница 77: ...Technical data 10 1 Labeling PAC1020 Equipment Manual 05 2020 L1V30610008B 01 75 ...
Страница 78: ......
Страница 93: ......
Страница 94: ......