Appendix
A.1 Modbus
PAC1020
Equipment Manual, 05/2020, L1V30610008B-01
85
Offset Number of
registers
Name
Format
Unit
Value range from ... to Access
to value (software)
read only / read
write
50011 2
Primary current
unsigned long
1 … 99999A
RW
50013 2
Secondary current
unsigned long
1, 5
RW
50019 2
Current direction
L1,L2,L3
unsigned long
0 … 7 bit-coded
Bit = 0 means normal,
Bit = 1 is inverse
.0 L1
.1 L2
.2 L3
RW
50025 2
Energy counter func-
tion
unsigned long
0 … 2 WORD-CODED
•
0 = import
•
1 = export
•
2 = net
HIWORD kVARh setting
LOWORD kWh setting
RW
50035 2
Digital output 0.0 ac-
tion
unsigned long
0 … 2
•
0 = no action
•
1 = switching output
•
2 = pulse output
RW
50037 2
Output 0.0 pulse type
index
unsigned long
0 … 3
•
0 = import kWh
•
1 = export kWh
•
2 = import kvarh
•
3 = export kvarh
RW
50039 2
Output 0.0 pulse ratio
(pulses per kWh/kvarh)
unsigned long
1-4000
RW
50041 2
Output 0.0 pulse
length
unsigned long
30-500
RW
50043 2
Digital output 0.0
Timeout
unsigned long
0.1 … 18000
Digital output remote
timeout = 1 … 18000
seconds
0 = disables timeout
(default)
RW
50045 2
Output 0.0 pulse divid-
er
unsigned long
0 … 3
•
0 = 1kWh
•
1 = 10kWh
•
2 = 100kWh
•
3 = 1000kWh
RW
Содержание 7KM1020-0BA01-1DA0
Страница 1: ......
Страница 2: ......
Страница 8: ...Table of contents PAC1020 6 Equipment Manual 05 2020 L1V30610008B 01 ...
Страница 22: ......
Страница 44: ...Commissioning 5 6 Checking the displayed measured values PAC1020 42 Equipment Manual 05 2020 L1V30610008B 01 ...
Страница 50: ...Operation 6 1 Device interface PAC1020 48 Equipment Manual 05 2020 L1V30610008B 01 ...
Страница 77: ...Technical data 10 1 Labeling PAC1020 Equipment Manual 05 2020 L1V30610008B 01 75 ...
Страница 78: ......
Страница 93: ......
Страница 94: ......